Free · NEC 2020 · No signup
NEC electrical calculators
built for the field
Voltage drop, wire sizing, ampacity, and conduit fill: every result cites the NEC table and article. Works on your phone on the jobsite.
-
Cited to the NEC
Table number and edition stated for every result. Default NEC 2020.
-
Built from NEC Chapter 9
Every constant is sourced directly from the NEC Chapter 9 tables, with the formula and assumptions shown on each tool page.
-
Jobsite-ready
Fast on any phone. No account required, no paywalls, no popups.
Calculators
Voltage Drop
AC and DC voltage drop calculations, NEC Chapter 9 resistance data.
-
Voltage Drop Calculator
Single- and three-phase AC drop. K-factor under #2 AWG, NEC Table 9 for #2 and larger. Flags the 3% and 5% NEC recommendations.
Open calculator -
DC Voltage Drop Calculator
DC circuits (solar, battery banks, marine) using NEC Chapter 9, Table 8 resistance values.
Open calculator -
Solar Voltage Drop Calculator
PV DC string and array conductors against the 2% and 3% solar design targets. Reports power loss; NEC Chapter 9, Table 8 resistance.
Open calculator -
3-Phase Voltage Drop Calculator
Three-phase voltage drop using the √3 multiplier. NEC Table 9 AC resistance, same method as the main VD tool.
Open calculator -
12V Voltage Drop Calculator
Automotive, RV, and battery systems. Defaults to 12V; override for 24V and 48V banks.
Open calculator -
Extension Cord Voltage Drop
Match a cord gauge (16-10 AWG) to a tool load. Practical 3% guideline; K-factor method.
Open calculator -
Marine Voltage Drop Calculator
Boat wiring per ABYC E-11: K = 10.75 copper formula, 3% critical and 10% non-critical limits, marine cable sizes 18 AWG to 4/0.
Open calculator -
Voltage Drop Chart
Printable max-run-distance tables at the 3% recommendation, for 120V and 240V, copper and aluminum, by AWG and load.
Open calculator
Wire & Conductor Sizing
Size conductors per NEC Table 310.16 with derating and voltage drop cross-checks.
-
Wire Size Calculator
Returns the minimum conductor for a load, distance, and target voltage drop. Checks NEC Table 310.16 ampacity, derating, and standard OCPD sizes.
Open calculator -
Wire Gauge Calculator
Enter a required ampacity, get the minimum AWG. NEC Table 310.16 with full derating: ambient, conductor count, and 110.14(C) termination cap.
Open calculator -
Wire Ampacity Calculator
Derated ampacity per NEC 310.15: ambient correction, conductor-count adjustment, and 110.14(C) termination cap.
Open calculator -
Wire Ampacity Chart
Printable NEC Table 310.16 base ampacities for copper and aluminum, 60/75/90C columns, 18 AWG to 2000 kcmil. Computed from the audited ampacity calculator.
Open calculator -
DC Wire Size Calculator
Sizes conductors for solar PV, battery banks, and 12/24/48V systems. Table 8 DC-resistance voltage drop plus Table 310.16 derated ampacity.
Open calculator -
AWG Calculator
AWG/kcmil ↔ mm² conversions from the published NEC Chapter 9 Table 8 areas, with the IEC 60228 metric cross-reference.
Open calculator -
Cable Size Calculator
Sizes each conductor of a multi-conductor cable when more than three current-carrying conductors are bundled, applying the NEC Table 310.15(C)(1) adjustment on top of Table 310.16 ampacity.
Open calculator -
Dwelling Service Conductor Calculator
Minimum copper and aluminum service or feeder conductor for a 100 to 400 amp single-phase dwelling under the NEC 310.12 83% allowance, with the standard Table 310.16 size for comparison.
Open calculator -
Ampacity Correction & Adjustment Calculator
Reads the NEC Table 310.15(B)(1) ambient temperature correction factor and Table 310.15(C)(1) conductor-count adjustment for a conductor, then reports the derated ampacity.
Open calculator -
Parallel Conductor Sizing Calculator
Total ampacity of conductors run in parallel under NEC 310.10(G): the 1/0 minimum, per-conductor ampacity times the number of sets, the shared-raceway Table 310.15(C)(1) derating, and the 250.122(F) grounding conductor per raceway.
Open calculator
Conduit Fill
NEC Chapter 9 Table 1 fill limits, Annex C conductor counts, and NEC 392 cable tray fill.
-
Conduit Fill Calculator
Mixed conductors in EMT, RMC, IMC, or PVC against the 53% / 31% / 40% limits in NEC Chapter 9, Table 1.
Open calculator -
Conduit Size Calculator
Minimum conduit trade size for your conductor bundle across EMT, RMC, IMC, and PVC Schedule 40/80, all in one comparison table.
Open calculator -
Cable Tray Fill Calculator
Multiconductor cable fill for ladder and ventilated trough trays per NEC Table 392.22(A), Columns 1 and 2, with the minimum standard tray width.
Open calculator -
Wireway Fill Calculator
Conductor fill for metal and nonmetallic wireways against the NEC 376.22(A) / 378.22 20% limit, minimum standard size, and the over-30-conductor adjustment flag.
Open calculator -
EMT Conduit Fill Calculator
Fill calculation locked to EMT. Minimum trade size and actual fill percentage for your conductor bundle.
Open calculator -
PVC Conduit Fill Calculator
PVC Schedule 40 and Schedule 80 fill per NEC Chapter 9. Separate Table 4 areas applied for each schedule.
Open calculator -
Conduit Fill Table
Max same-size conductor counts from NEC 2020 Annex C: EMT, IMC, RMC, PVC Sch 40/80. THHN/THWN-2 and XHHW-2. Printable.
Open calculator
Conduit & Cable Installation
Physical conduit and cable installation rules: thermal expansion, raceway support, and cable securing.
-
PVC Conduit Expansion Calculator
Thermal length change of a straight PVC conduit run from the temperature swing per NEC Table 352.44, with the 1/4 inch expansion-fitting threshold and an optional direct-sunlight allowance.
Open calculator -
Conduit Support Spacing Calculator
Maximum support spacing for PVC, RMC, EMT, FMC, and LFMC by trade size per NEC 352.30/344.30/358.30/348.30/350.30, with the box-securing distance and a support-point count for your run.
Open calculator -
Cable Support Spacing Calculator
Maximum support interval for NM (Romex), AC, MC, and SE cable per NEC 334.30/320.30/330.30, with the box-securing distance and a support-point count for your run.
Open calculator -
RTRC Conduit Expansion Calculator
Thermal length change of a straight RTRC (fiberglass) conduit run from the temperature swing per NEC Table 355.44, with the 1/4 inch expansion-fitting threshold and an optional direct-sunlight allowance.
Open calculator -
Maximum Bends Between Pull Points Calculator
Add the bends in a conduit run and check the total against the NEC 360-degree limit (four quarter bends) between pull points per 358.26/344.26/352.26 and the other .26 sections, with offsets counted as two bends.
Open calculator -
Cable Protection Setback Calculator
Check whether a cable or raceway in wood framing clears the NEC 300.4 1-1/4 inch setback or needs a 1/16 inch steel nail plate, for bored holes (300.4(A)(1)), notches (300.4(A)(2)), and parallel runs (300.4(D)).
Open calculator
Boxes & Enclosures
Outlet, device, and junction box sizing per NEC Article 314.
-
Box Fill Calculator
Required outlet, switch, or junction box volume per NEC 314.16(B): conductor, clamp, support-fitting, device-yoke, and grounding allowances against the box capacity.
Open calculator -
Pull Box Size Calculator
Minimum pull and junction box dimensions per NEC 314.28(A): straight pulls at 8x the largest raceway and angle or U pulls at 6x plus the row sum, for conductors 4 AWG and larger.
Open calculator -
Fan & Luminaire Box Support Calculator
Can an outlet box support that paddle fan or luminaire per NEC 314.27? Checks the 35 lb unmarked fan-box limit, the 70 lb fan ceiling, and the 50 lb luminaire allowance, or flags independent support.
Open calculator
Circuit Protection
Overcurrent device sizing per NEC 210.20, 240.6, the 240.4 conductor-protection rules, Article 430 motor circuits, and Article 625 EV chargers.
-
Breaker Size Calculator
Standard NEC 240.6(A) breaker for a load with the 125% continuous rule, plus the minimum conductor the breaker can legally protect.
Open calculator -
Continuous Load Calculator
Apply the NEC 210.20(A) continuous-load rule both ways: size a breaker for a continuous load (125%), or find the maximum load an existing breaker can carry (the 80% rule).
Open calculator -
Fuse Size Calculator
Standard NEC 240.6(A) fuse for a general-use load, including the fuse-only 1/3/6/10/601 A ratings, with the 125% continuous rule and the minimum conductor per 240.4(B)/(D).
Open calculator -
Motor Breaker Sizing Calculator
Motor branch-circuit breaker or fuse per NEC Article 430: full-load current from Table 430.250, Table 430.52 device percentages, and the 430.22 conductor.
Open calculator -
GFCI Breaker Sizing Calculator
Check whether NEC 2020 210.8 requires GFCI protection for a location, then size the GFCI breaker and conductor with the 1-pole or 2-pole call.
Open calculator -
AFCI Requirement & Breaker Sizing Calculator
Check whether NEC 2020 210.12 requires arc-fault protection in a dwelling room, then size the AFCI breaker and conductor, with the 210.12(D) extension rule and the AFCI-vs-GFCI distinction.
Open calculator -
Surge-Protective Device (SPD) Requirement Calculator
Check whether NEC 2020 230.67 requires a service surge-protective device, which Type (1 or 2) satisfies it, where it mounts, and how the 230.67(D) replacement trigger applies.
Open calculator -
EV Charger Circuit Calculator
Branch-circuit breaker and wire for an EV charger: NEC Article 625 continuous-load rule sizes the circuit at 125% of the charger rating, with SAE J1772 Level 1/2 presets.
Open calculator -
Transformer Sizing Calculator
Maximum primary and secondary overcurrent device for a transformer 1000V or less per NEC Table 450.3(B): rated current from kVA and the 125/167/250/300% limits.
Open calculator -
MCA & MOCP Calculator
HVAC minimum circuit ampacity and maximum overcurrent protection per NEC Article 440: 125% conductor (440.33), 175%/225% device (440.22), and the Table 310.16 wire size.
Open calculator -
Room Air Conditioner Branch Circuit Calculator
Branch circuit for a cord-and-plug room air conditioner per NEC 440.62: the 80% dedicated-circuit and 50% shared-circuit rules, and the minimum standard breaker.
Open calculator -
Motor Overload Protection Calculator
Running-overload relay for a motor per NEC 430.32: 125% or 115% of nameplate full-load current, with the 430.32(C) increase to 140% or 130%.
Open calculator -
Motor & HVAC Disconnect Sizing Calculator
Minimum disconnect ampere rating for a motor (NEC 430.110) or an A/C compressor (NEC 440.12): 115% of the table full-load current, or of the greater of RLA or BCSC.
Open calculator -
Motor & A/C Equipment Disconnect Location Calculator
Where the disconnect has to go per NEC 440.14 (A/C) and 430.102(B) (motor): within sight (visible and within 50 ft), readily accessible, and the lockable exception.
Open calculator -
Motor Full-Load Current Calculator
Look up motor full-load current from NEC Table 430.248/430.250 by horsepower and voltage (430.6(A)(1)), with the 430.22 branch-circuit conductor minimum ampacity.
Open calculator -
Multi-Motor Feeder Calculator
Size a feeder for a group of motors per NEC 430.24 (125% of the largest motor FLC plus the other motors) and 430.62(A) (largest branch device plus the other FLCs, rounded down).
Open calculator -
Several Motors on One Branch Circuit Calculator
Put several motors on one branch circuit per NEC 430.53: the (A) small-motor allowance (each 1 hp and 6 A or less), the (B) smallest-motor device, and the (C) group-installation device.
Open calculator -
Feeder Tap Conductor Size Calculator
Size a feeder tap conductor under the NEC 240.21(B) 10-foot and 25-foot tap rules: required ampacity (1/10 or 1/3 of the feeder OCPD) and the smallest Table 310.16 conductor.
Open calculator -
Transformer Secondary Conductor Calculator
Size a transformer secondary conductor under the NEC 240.21(C) rules: the reflected primary OCPD, the 10-foot and 25-foot secondary tap rules, and the smallest Table 310.16 conductor.
Open calculator -
Generator Conductor Size Calculator
Size generator output conductors under the NEC 445.13(A) 115%-of-nameplate rule: nameplate current from kVA and the smallest Table 310.16 copper or aluminum wire.
Open calculator -
Welder Circuit Calculator
Size a single arc welder branch circuit per NEC Article 630: the Table 630.11(A) duty-cycle-adjusted conductor from Table 310.16 and the 630.12 200% overcurrent device.
Open calculator -
Group Welder Feeder Demand Calculator
Size a feeder to a group of arc welders per NEC 630.11(B): the 100/85/70/60% diversity on each welder’s 630.11(A) current, the Table 310.16 conductor, and the 630.12(B) feeder OCPD.
Open calculator -
Capacitor Conductor & OCPD Calculator
Size power-capacitor circuit conductors per NEC 460.8(A): 135% of the rated capacitor current (from kVAR or entered directly) and the smallest Table 310.16 copper or aluminum wire.
Open calculator -
Water Heater Circuit Calculator
Size an electric water heater branch circuit per NEC 422.13: the 125% continuous-load minimum breaker and conductor, plus the 422.11(E) 150% breaker maximum window.
Open calculator -
Space-Heating Circuit Calculator
Size a fixed electric space-heating branch circuit (baseboard, unit heater, furnace) per NEC 424.3(B): 125% of the heater plus associated motor, with the 424.22(B) 48 A/60 A subdivision flag.
Open calculator -
Range & Cooking Appliance Branch Circuit Calculator
Minimum branch-circuit rating for a household range, wall oven, or cooktop per NEC 210.19(A)(3): the 40 A range floor, the Table 220.55 demand basis, and the tap and neutral allowances.
Open calculator -
Fire Pump Supply Conductor Calculator
Size fire pump supply conductors per NEC 695.6(B)(1): 125% of the fire pump plus jockey pump motor FLC, 100% of accessory load, and the smallest Table 310.16 copper or aluminum wire.
Open calculator -
Service Disconnect Number & Rating Calculator
How many service disconnects the 2020 NEC allows and the minimum rating: the 230.71 single-disconnect change, the 230.79 floors (15/30/100/60 A), and the 230.80 combined rating.
Open calculator -
Panelboard Overcurrent Protection Calculator
Check whether a breaker or fuse may protect a panelboard per NEC 408.36 (rated not greater than the panel) and find the largest permitted device, rounded down to a 240.6(A) standard.
Open calculator -
Receptacle Rating & Branch-Circuit Load Calculator
Which receptacle a branch circuit may carry and how much load it may serve per NEC 210.21(B) and 210.23: permitted receptacle ratings, the Table 210.21(B)(2) maximum, and the 80%/50% limits.
Open calculator
Load Calculations
Service and feeder sizing per NEC Article 220.
-
Electrical Load Calculator
Dwelling service load per NEC 220.82 (optional method): floor area, appliances, and HVAC in; calculated amps and standard service size out.
Open calculator -
Existing Dwelling Load Calculator
Existing dwelling addition per NEC 220.83: check whether an existing service can carry an added load, with the 8 kVA/40% split and the 220.60 noncoincident larger-of-HVAC rule.
Open calculator -
Existing Load by Metered Demand Calculator
Existing load from measured demand per NEC 220.87: recorded maximum demand at 125% plus the new load, checked against the feeder ampacity or service rating, with the spare-capacity figure.
Open calculator -
Multifamily Dwelling Load Calculator
Apartment building feeder and service load per the NEC 220.84 optional method: per-unit connected load at 100% nameplate, the Table 220.84 demand factor by unit count, and house loads added after.
Open calculator -
Two-Family Dwelling Load Calculator
Duplex feeder and service load per NEC 220.85: the Article 220 Part III standard calculation for the two units run against the 220.84 optional method for three identical units, lesser governs.
Open calculator -
Residential Electrical Load Calculator
Dwelling service load by the NEC Article 220 standard method: category-by-category demand factors (Tables 220.42/220.54/220.55, noncoincident HVAC, largest-motor adder).
Open calculator -
Mobile Home Electrical Load Calculator
Single mobile or manufactured home supply per NEC 550.18: lighting on the home’s outside dimensions, Table 220.55 range, 220.54 dryer, noncoincident HVAC, and the 100 A minimum service (550.32(C)).
Open calculator -
Commercial Load Calculator
Non-dwelling load per NEC 220 Part III: general lighting by occupancy (Table 220.12), receptacle, kitchen, and show-window loads to a service size.
Open calculator -
Service Size Calculator
From a known load: minimum service disconnect (NEC 230.79), service-entrance conductor (230.42, Table 310.16), and grounding electrode conductor (Table 250.66) with the 250.66(A)/(B) caps.
Open calculator -
Range / Cooktop Demand Load Calculator
Household cooking demand per NEC Table 220.55 Column C: one or more identical ranges, the Note 1 step over 12 kW, and the Note 4 branch-circuit cases for ranges, ovens, and cooktops.
Open calculator -
Electric Dryer Demand Load Calculator
Household electric clothes dryer demand per NEC 220.54: the 5000 VA (or nameplate) per-dryer minimum and the Table 220.54 multi-dryer demand factors, with demand amps at 240 V.
Open calculator -
Commercial Kitchen Equipment Demand Calculator
Commercial kitchen equipment demand per NEC Table 220.56: the demand factor by unit count plus the two-largest-loads floor made explicit, with demand kVA, kW, and amps.
Open calculator -
Fixed Appliance Demand Load Calculator
Dwelling fastened-in-place appliance demand per NEC 220.53: the 75% demand factor for four or more appliances (100% otherwise), with the connected load and demand amps.
Open calculator -
Commercial Receptacle Load Calculator
Non-dwelling receptacle load per NEC 220.14(I) and Table 220.44: 180 VA per strap, first 10 kVA at 100% and the rest at 50%, plus the 220.14(K) office 1 VA/ft² floor.
Open calculator -
Neutral Load Calculator
Feeder and service neutral load per NEC 220.61: the maximum unbalance with the range and dryer 70% reduction, the over-200 A 70% demand factor, and the nonlinear no-reduction rule.
Open calculator -
Minimum Branch Circuits Calculator
Minimum dwelling branch circuits per NEC 210.11: general-purpose circuits from the 3 VA/ft² general lighting load plus the required small-appliance, laundry, bathroom, and garage circuits.
Open calculator -
Receptacle Spacing Calculator
Minimum dwelling receptacles per NEC 210.52: the 6 ft / 12 ft wall rule (210.52(A)) and the 24 in / 4 ft kitchen countertop rule (210.52(C)(1)), with the count per run.
Open calculator -
Show Window & Sign Lighting Load Calculator
Show-window and sign loads per NEC 220.43(A)/220.14(G) and 220.14(F): 200 VA per linear foot of show window plus 1200 VA per required sign circuit, with the 125% continuous figure and amps.
Open calculator -
Multi-Outlet Assembly Load Calculator
Fixed multioutlet assembly load per NEC 220.14(H): 180 VA per 5 ft where appliances are unlikely to run at once, or per 1 ft where likely, with the connected load and amps.
Open calculator -
Track Lighting Load Calculator
Track lighting load per NEC 220.43(B): 150 VA per 2 ft of lighting track (or fraction thereof) at 100% in other-than-dwelling occupancies, with the 125% continuous figure and amps.
Open calculator -
Receptacles Per Circuit Calculator
How many receptacles on a branch circuit: NEC 220.14(I) 180 VA per strap caps a 20 A circuit at 13 and a 15 A at 10 in non-dwellings, while dwelling units have no NEC limit.
Open calculator
Grounding & Bonding
Equipment grounding and bonding conductor sizing per NEC Article 250.
-
Equipment Grounding Conductor Size Calculator
Minimum equipment grounding conductor from the OCPD rating per NEC Table 250.122, with the 250.122(B) proportional upsize for voltage-drop conductors and the 250.122(F) parallel-raceway rule.
Open calculator -
Grounding Electrode Conductor Size Calculator
Minimum grounding electrode conductor from the service conductor size per NEC Table 250.66, with the 250.66(A) ground-rod and 250.66(B) concrete-encased caps and parallel equivalent-area handling.
Open calculator -
Bonding Jumper Size Calculator
Minimum main, system, or supply-side bonding jumper and grounded conductor from the phase conductor per NEC Table 250.102(C)(1), including the Note 1 12.5% rule above 1100 kcmil and parallel equivalent-area handling.
Open calculator -
Metal Water Pipe & Structural Metal Bonding Calculator
Bonding jumper for metal water pipe, gas pipe, or structural steel per NEC 250.104: Table 250.102(C)(1) with the 3/0 Cu / 250 kcmil Al water-pipe cap, Table 250.122 off the energizing OCPD for other piping, and the uncapped table for structural metal.
Open calculator -
Ground Rod Resistance & Supplemental Rule Calculator
Whether a single rod, pipe, or plate electrode needs a supplemental electrode per NEC 250.53(A)(2): the 25-ohm exception, the unmeasured default, and the 250.53(A)(3) 6 ft spacing between two electrodes.
Open calculator -
Separate Structure Grounding & Bonding Calculator
Grounding and bonding for a detached garage, shed, or outbuilding fed by a feeder or branch circuit per NEC 250.32: when a grounding electrode is required, when to run an equipment grounding conductor, and when the neutral is isolated at the structure.
Open calculator -
Intersystem Bonding Termination Calculator
Whether an intersystem bonding termination for communications systems meets NEC 250.94: the three-terminal minimum, accessibility, enclosure clearance, the 6 AWG copper bond, and the listing requirement, at the service or a structure disconnect.
Open calculator
Solar / PV Systems
Photovoltaic conductor and overcurrent sizing per NEC Article 690.
-
Solar PV Wire Size Calculator
PV source and output circuit conductors and fuses per NEC 690.8 and 690.9: 125% maximum current from Isc, the larger of the two 690.8(B) paths on Table 310.16, and the standard OCPD rating.
Open calculator -
Solar 120% Rule Calculator
Load-side PV and storage interconnection per NEC 705.12(B)(3): the sum method and the 120% rule tested from 125% of the source output current, with the maximum source and largest standard backfed OCPD a busbar allows.
Open calculator
Installation & Clearances
Physical installation, placement, and clearance rules for electrical equipment, dwelling outlets, overhead spans, pools, and bathrooms per NEC Articles 110, 210, 225, 230, 406, 410, and 680.
-
Working Space Clearance Calculator
Required working space in front of equipment 600 V or less per NEC 110.26(A): the depth from Table 110.26(A)(1) by Condition and voltage to ground, plus the 30 in width and 6.5 ft headroom.
Open calculator -
Working Space Entrance & Egress Calculator
Entrance and egress for a working space per NEC 110.26(C): when equipment rated 1200 A or more and over 6 ft wide needs an exit at each end, the 24 in by 6.5 ft minimum opening, and the 800 A personnel-door panic-hardware rule.
Open calculator -
Overhead Conductor Clearance Calculator
Minimum vertical clearance of an overhead service drop or feeder per NEC 230.24 and 225.18: 10/12/15/18 ft over sidewalks, driveways, and streets by voltage to ground, plus 24.5 ft over rails and 8 ft above roofs.
Open calculator -
Dedicated Equipment Space Calculator
Dedicated equipment space above a switchboard, panelboard, or MCC per NEC 110.26(E): 6 ft above the equipment, or up to the structural ceiling indoors, kept clear of piping and ducts.
Open calculator -
Conductor Clearance From Buildings Calculator
Clearance of overhead conductors from buildings per NEC 230.9 and 225.19: 3 ft from openable windows, doors, porches, signs, and walls for a service drop or outside feeder, with the fixed-window and above-window carve-outs.
Open calculator -
Swimming Pool & Spa Equipment Clearance Calculator
Pool and spa equipment clearances per NEC 680.22 and 680.43: receptacles 6 to 20 ft from the water (10 ft for an indoor spa), luminaires 12 ft above, and switches 5 ft back, with a compliance check on a measured placement.
Open calculator -
Swimming Pool & Spa Equipotential Bonding Calculator
Pool and spa equipotential bonding per NEC 680.26: which parts must be bonded, the 8 AWG solid copper conductor, the 3 ft perimeter surface, and the 5 ft horizontal by 12 ft vertical zone for nearby fixed metal parts.
Open calculator -
Pool & Spa Equipment Maintenance Disconnect Calculator
Where the maintenance disconnecting means for pool and spa equipment goes per NEC 680.12: readily accessible, within sight (visible and within 50 ft), and at least 5 ft from the water unless a permanent barrier intervenes, with a compliance check.
Open calculator -
Swimming Pool Underwater Luminaire Requirement Calculator
Underwater pool luminaires per NEC 680.23: the 150 V limit between conductors, when the branch circuit must be GFCI protected (above the 15 V AC / 30 V DC contact limit), and the 18 in minimum lens depth below the water (4 in absolute floor).
Open calculator -
Bathtub & Shower Zone Clearance Calculator
Bathtub and shower zone per NEC 406.9(C) and 410.10(D): no receptacles or hanging luminaires within 3 ft horizontally and 8 ft vertically of the rim, plus the damp/wet listing for lights over the tub or shower.
Open calculator -
Hydromassage Bathtub Receptacle & GFCI Calculator
Hydromassage (whirlpool) tub compliance per NEC 680.71/680.73/680.74: the readily accessible GFCI and individual branch circuit, the 6 ft / 125 V / 30 A nearby-receptacle GFCI rule, the 12 in service-opening rule, and the 8 AWG solid copper bond, with a compliance verdict.
Open calculator -
Clothes Closet Luminaire Clearance Calculator
Clothes closet light rules per NEC 410.16: which luminaires are permitted, the 12 in or 6 in clearance from the storage space by type, and the 24 in / 12 in / 6 ft storage-space envelope the clearance is measured to.
Open calculator -
Recessed Luminaire Clearance Calculator
Recessed can-light clearances per NEC 410.116: 1/2 in from combustibles and 3 in from thermal insulation (none above) for a non-Type IC fixture, versus the Type IC contact allowance, with a compliance verdict.
Open calculator -
Tamper-Resistant & Weather-Resistant Receptacle Calculator
Where a receptacle must be tamper-resistant (NEC 406.12 dwellings, guest rooms, child care, schools, medical offices, assembly, dorms) or weather-resistant (NEC 406.9 damp and wet locations), with the four 406.12 exceptions and the extra-duty cover rule.
Open calculator -
Receptacle Replacement Requirement Calculator
What a replacement receptacle must be under NEC 406.4(D): grounding type where a ground exists, the three options where none does (incl. the GFCI "No Equipment Ground" and two-prong cases), plus GFCI (210.8), AFCI (210.12), tamper-resistant (406.12), and weather-resistant (406.9) carried onto the new device.
Open calculator -
Receptacle Mounting Position Calculator
Where and how a receptacle may be mounted under NEC 2020 406.5: the 406.5(G) face-up rules for countertops and work surfaces (406.5(G)(1), listed assembly only) and the area below a sink (406.5(G)(2), new in 2020), plus the 406.5(A)/(B) and 314.20 flush vs set-back box rules and the 406.5(D) face position.
Open calculator -
Dwelling Lighting Outlet Requirements Calculator
Where a dwelling lighting outlet is required per NEC 210.70(A): the wall switch-controlled outlet in habitable rooms and baths (with the kitchen/bathroom exclusion), hallways, garages, and outdoor entrances, plus the six-riser stairway switching rule and the storage/equipment-space condition.
Open calculator -
Dwelling Required Receptacle Outlets Calculator
Where a dwelling receptacle outlet is required per NEC 210.52 and the minimum count: kitchen small-appliance circuits, countertops, bathrooms (3 ft of each basin), outdoor, laundry, garages (one per vehicle bay), basements, hallways 10 ft or more, and foyers over 60 sq ft.
Open calculator -
HVAC & Service Equipment Service Receptacle Calculator
Where a 125 V, 15/20 A service receptacle is required per NEC 210.63: within 25 ft and on the same level of HVAC and refrigeration equipment (210.63(A)), and in the same room or area as indoor service equipment and 110.26(E) dedicated-space equipment (210.63(B)), with the load-side and evaporative-cooler rules.
Open calculator -
Snap Switch Mounting Height & Grouping Calculator
Switch and breaker accessibility per NEC 404.8: the 6 ft 7 in (2.0 m) maximum handle height with the busway, adjacent-equipment, and hookstick exceptions (404.8(A)), and the 300 V limit on the voltage between adjacent ganged devices unless an identified barrier is installed (404.8(B)).
Open calculator -
Emergency Disconnect Requirement Calculator
The NEC 230.85 emergency disconnect for one- and two-family dwellings: the readily accessible outdoor location, the grouping rule for more than one disconnect, and the three marking labels for a service, meter, or other supply-side disconnect, with a compliance check.
Open calculator -
Appliance Disconnecting Means Calculator
What serves as the disconnecting means for an appliance per NEC 422 Part III: the branch breaker at or below 300 VA / 1/8 hp (422.31(A)), a switch within sight or lockable above that (422.31(B)/(C)), an accessible plug (422.33), and the unit-switch allowance (422.34), with a compliance check.
Open calculator -
Sign & Outline Lighting Outlet Requirement Calculator
When the NEC requires a sign/outline lighting outlet per 600.5(A): one outlet at each pedestrian-accessible entrance to each tenant space, a dedicated branch circuit rated at least 20 A, the 600.5(B) rating ceiling (20 A non-neon / 30 A neon), and the 1200 VA minimum computed load per required circuit (220.14(F)).
Open calculator -
Show Window Receptacle Outlet Calculator
How many receptacle outlets a show window requires per NEC 210.62: one 125 V, 15 or 20 A receptacle within 18 in of the top for each 12 linear feet or major fraction (6 ft or more) of show window width, measured at the maximum width. The receptacle-count sibling of the Show Window & Sign Lighting Load tool.
Open calculator -
Service Drop Point of Attachment Height Calculator
The minimum point-of-attachment height for an overhead service drop per NEC 230.26: the 10 ft floor above finished grade and the higher 230.24(B) span clearance that governs over a driveway (12 ft) or a street or truck-traffic area (18 ft), with a compliance check.
Open calculator -
Service Disconnect Grouping & Load Marking Calculator
The NEC 230.72 / 230.70 installation rules for the service disconnecting means: grouping the two to six disconnects (230.72(A)), the service-disconnect (230.70(B)) and load-served (230.72(A)) markings, 230.70(C) suitability, and the 230.72(B) remote rule for fire-pump and standby disconnects, with a compliance check.
Open calculator -
Separate Structure Disconnecting Means Calculator
The disconnecting means for a detached garage, shed, or outbuilding fed by a feeder or branch circuit per NEC 225.31/225.32/225.33: whether a disconnect is required, the readily-accessible nearest-the-entrance location rule with its four exceptions, and the six-disconnect maximum (single enclosure still permitted, unlike the service rule), with a compliance check.
Open calculator -
Overcurrent Device Location & Accessibility Calculator
Where a panel, breaker, or fused switch may go under NEC 240.24: the 6 ft 7 in (2.0 m) maximum handle height and readily accessible rule (240.24(A)), each occupant's access (240.24(B)), and the physical-damage, clothes-closet, bathroom, and over-the-stairs prohibitions (240.24(C) through (F)), with a compliance check.
Open calculator -
Guest Room / Guest Suite Receptacle Outlets Calculator
How many receptacle outlets a hotel, motel, or dormitory guest room or guest suite requires per NEC 210.60: the 210.52(A) 6 ft / 12 ft wall count, the 210.52(D) bathroom basin receptacle, and the 210.60(B) two-readily-accessible floor, with the behind-the-bed guard and permanent-cooking (all of 210.52) rules.
Open calculator
Reference & exam prep
Beyond the calculators: study tools, printable cards, and code-adoption lookups.
-
Journeyman Practice Test
20 exam-style NEC questions with instant grading, the arithmetic worked out, and the governing table cited on every answer.
Take the test -
Master Practice Test
20 master-level NEC questions weighted toward motor and feeder calculations, transformer sizing, and grounding, each graded with the arithmetic and code reference shown.
Take the test -
Electrical Calculations Practice Test
20 almost entirely worked NEC calculation problems: voltage drop, conduit and box fill, ampacity, sizing, grounding, and transformers, each linked to the calculator that solves it.
Take the test -
Grounding and Bonding Practice Test
20 NEC Article 250 questions on the grounding electrode system, bonding jumpers, equipment grounding conductors, and separately derived systems, graded with the code reference on every answer.
Take the test -
Printable Reference Cards
Free PDF quick cards for the truck: voltage-drop max-run distances and AWG ↔ mm² conversions, computed by the same code as the calculators.
Get the PDFs -
NEC Adoption by State
Which National Electrical Code edition every state enforces: statewide vs. local adoption, effective dates, and amendment notes.
Look up your state -
NEC Code Quickstart (Book)
The twelve calculations every exam and job site come back to, each worked start to finish with the exact code reference. Kindle and paperback on Amazon.
View on Amazon