Voltage Drop Calculator
Calculate AC voltage drop on single-phase or three-phase circuits using National Electrical Code (NEC) 2020 conductor resistance: the K-factor for conductors smaller than #2 AWG and Chapter 9 Table 9 AC resistance for #2 and larger. Results flag compliance against the 3% branch and 5% combined feeder + branch recommendations in NEC 210.19 and 215.2.
Results
- Voltage drop
- -
- Percentage
- -
- Voltage at load
- -
Awaiting calculation…
Show calculation details
- Method
- -
- Resistance (R, 75°C)
- -
- Circular mils
- -
Conductors smaller than #2 AWG use the K-factor (R = K × 1000 / circular mils, K = 12.9 copper / 21.2 aluminum). #2 AWG and larger use NEC Chapter 9 Table 9 AC resistance (PVC conduit, 75°C). Unity power factor.
How to use this calculator
- Enter source voltage and select phase configuration (single or three).
- Enter load current in amps and the one-way circuit distance in feet.
- Select conductor material and AWG size.
- Results update as you adjust inputs. The status badge indicates compliance with the NEC 3% branch and 5% combined recommendations.
NEC reference
Conductor resistance comes from NEC 2020 Chapter 9. For conductors smaller than #2 AWG the calculator uses the K-factor (K = 12.9 for copper, 21.2 for aluminum, derived from Table 8). For #2 AWG and larger it uses Table 9 AC resistance (PVC conduit), which accounts for the skin and proximity effects the K-factor misses on large conductors. Values are taken at the published 75°C basis at unity power factor. Compliance status references NEC 210.19(A)(1) Informational Note No. 4 and NEC 215.2(A)(1) Informational Note No. 2.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
Voltage drop formula
Voltage drop is the conductor resistance times the current over the round-trip length:
Single-phase: VD = 2 × R × I × L / 1000
Three-phase: VD = √3 × R × I × L / 1000
R is resistance in ohms per 1000 ft, I is current in amps, and L is the one-way distance in feet. The 2× factor on single-phase accounts for the round trip; three-phase uses √3 for the line-to-line relationship, which works out to about 86.6% of the single-phase drop. For conductors below #2 AWG, R comes from the K-factor (R = K × 1000 / circular mils); for #2 and larger it comes directly from NEC Chapter 9 Table 9. Circular-mil and DC-resistance data live in Table 8.
Worked example
A 20A load on #12 copper, 240V single-phase, 100 feet one way:
# 12 copper is smaller than #2 → K-factor, K = 12.9
R = 12.9 × 1000 / 6,530 cmil = 1.976 Ω/1000 ft
VD = 2 × (1.976 / 1000) × 20 × 100 = 7.90 V
VD% = 7.90 / 240 = 3.29%
At 3.29% this exceeds the NEC 210.19 branch-circuit recommendation of 3%. It is acceptable only as part of a combined feeder-plus-branch budget under NEC 215.2. Stepping up to #10 copper drops it to about 2.07%, back within the 3% branch recommendation.
Common mistakes
- One-way vs round-trip distance. Enter the one-way run length. The calculator applies the 2× (single-phase) or √3 (three-phase) multiplier. Entering the there-and-back length double-counts the conductor.
- K-factor on large conductors. The K-factor shortcut (VD = 2KIL/CM) tracks DC resistance and diverges from real AC resistance on large conductors as skin and proximity effects grow. This tool switches to Table 9 AC resistance at #2 AWG for that reason.
- Confusing voltage drop with ampacity. These are separate checks. A conductor can satisfy its ampacity rating and still fail voltage drop on a long run; size for the worse of the two.
- Using this tool for DC. This is an AC calculator. DC drop on solar, battery, and automotive circuits uses DC resistance; use a dedicated DC tool.
Frequently asked questions
What is the NEC limit for voltage drop?
The NEC does not set a hard limit. NEC 210.19 recommends no more than 3% drop on a branch circuit and NEC 215.2 recommends 5% combined on feeder plus branch. Both appear as informational notes, so they carry recommendation weight at the federal level. Some local jurisdictions adopt them as enforceable through amendments; check your adopted code.
Does the NEC require voltage drop calculations?
No. The 3% and 5% figures are informational notes in NEC 210.19 and 215.2, not mandatory rules. Voltage drop remains a functional design constraint regardless of code: motors, electronics, and lighting misbehave with excessive drop. Some local amendments make the calculation mandatory, and many engineering specs require it. Confirm your jurisdiction's amendments.
How do I calculate voltage drop on a three-phase circuit?
Use the √3 multiplier in place of the 2× used for single-phase: VD = √3 × R × I × L / 1000, where R is conductor resistance per 1000 ft and L is one-way distance. For the same conductor, current, and length, three-phase drop is about 86.6% (√3/2) of the single-phase value. Select "Three-phase" and the calculator applies the factor automatically.
Should I use one-way or total circuit length?
Enter the one-way length, source to load. The calculator applies the round-trip multiplier internally. Entering the total there-and-back length double-counts the conductor and roughly doubles the result.
What's an acceptable voltage drop for motor circuits?
NEC 430 doesn't mandate a figure, but motors are sensitive: low terminal voltage raises current and heat, and starting torque falls with the square of voltage. Many designers hold motor branches to 3% and total to 5%. This calculator assumes unity power factor; motors run at a lower power factor, which increases drop, so for precise motor work use a calculator that accepts a custom power factor.
When does voltage drop matter most?
Long runs, high current, and small conductors. Drop scales with current and length and inversely with conductor cross-section, so a long feeder or a small-AWG circuit pushed near its ampacity is where it bites. It also matters for sensitive loads (VFDs, control circuits, and LED drivers), where low voltage causes nuisance faults.
Guides
- How to Calculate Voltage Drop Percentage: the 3% rule and the K-factor method, worked step by step.
- Wire Size for a 200-Foot, 30-Amp Circuit: why the ampacity-minimum conductor fails on a long run.
Related calculators
- Wire Size Calculator: size a conductor for a target ampacity and voltage drop.
- DC Voltage Drop Calculator: for solar, battery, and automotive DC circuits.
- Wire Ampacity Calculator: conductor ampacity with temperature and conduit-fill derating.
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
For deeper NEC training on conductor sizing and voltage drop, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.