Voltage Drop Chart
Maximum one-way run distance, in feet, that keeps voltage drop within the NEC 3% recommendation, by conductor size and load. Computed with the same method as our Voltage Drop Calculator (NEC Chapter 9; unity power factor, 75°C). Print it, or use the calculator for exact conditions.
120 V single-phase, copper
Max one-way distance (ft) at ≤3% drop. "-" means the load exceeds the conductor's 75°C ampacity (NEC Table 310.16); voltage drop is moot.
| AWG/kcmil | 15 A | 20 A | 30 A | 40 A | 50 A | 100 A |
|---|---|---|---|---|---|---|
| 14 | 38 ft | 28 ft | - | - | - | - |
| 12 | 60 ft | 45 ft | - | - | - | - |
| 10 | 96 ft | 72 ft | 48 ft | - | - | - |
| 8 | 153 ft | 115 ft | 76 ft | 57 ft | 46 ft | - |
| 6 | 244 ft | 183 ft | 122 ft | 91 ft | 73 ft | - |
| 4 | 388 ft | 291 ft | 194 ft | 145 ft | 116 ft | - |
| 3 | 489 ft | 367 ft | 244 ft | 183 ft | 146 ft | 73 ft |
| 2 | 631 ft | 473 ft | 315 ft | 236 ft | 189 ft | 94 ft |
| 1 | 799 ft | 600 ft | 399 ft | 300 ft | 240 ft | 120 ft |
| 1/0 | 1000 ft | 750 ft | 500 ft | 375 ft | 300 ft | 150 ft |
| 2/0 | 1200 ft | 899 ft | 600 ft | 449 ft | 359 ft | 179 ft |
| 3/0 | 1558 ft | 1168 ft | 779 ft | 584 ft | 467 ft | 233 ft |
| 4/0 | 1935 ft | 1451 ft | 967 ft | 725 ft | 580 ft | 290 ft |
240 V single-phase, copper
Max one-way distance (ft) at ≤3% drop. "-" means the load exceeds the conductor's 75°C ampacity (NEC Table 310.16); voltage drop is moot.
| AWG/kcmil | 15 A | 20 A | 30 A | 40 A | 50 A | 100 A |
|---|---|---|---|---|---|---|
| 14 | 76 ft | 57 ft | - | - | - | - |
| 12 | 121 ft | 91 ft | - | - | - | - |
| 10 | 193 ft | 144 ft | 96 ft | - | - | - |
| 8 | 307 ft | 230 ft | 153 ft | 115 ft | 92 ft | - |
| 6 | 488 ft | 366 ft | 244 ft | 183 ft | 146 ft | - |
| 4 | 776 ft | 582 ft | 388 ft | 291 ft | 232 ft | - |
| 3 | 978 ft | 734 ft | 489 ft | 367 ft | 293 ft | 146 ft |
| 2 | 1263 ft | 947 ft | 631 ft | 473 ft | 378 ft | 189 ft |
| 1 | 1599 ft | 1200 ft | 799 ft | 600 ft | 480 ft | 240 ft |
| 1/0 | 2000 ft | 1500 ft | 1000 ft | 750 ft | 600 ft | 300 ft |
| 2/0 | 2400 ft | 1799 ft | 1200 ft | 899 ft | 719 ft | 359 ft |
| 3/0 | 3116 ft | 2337 ft | 1558 ft | 1168 ft | 935 ft | 467 ft |
| 4/0 | 3870 ft | 2903 ft | 1935 ft | 1451 ft | 1161 ft | 580 ft |
240 V single-phase, aluminum
Max one-way distance (ft) at ≤3% drop. "-" means the load exceeds the conductor's 75°C ampacity (NEC Table 310.16); voltage drop is moot.
| AWG/kcmil | 15 A | 20 A | 30 A | 40 A | 50 A | 100 A |
|---|---|---|---|---|---|---|
| 12 | 73 ft | 55 ft | - | - | - | - |
| 10 | 117 ft | 88 ft | 58 ft | - | - | - |
| 8 | 186 ft | 140 ft | 93 ft | 70 ft | - | - |
| 6 | 297 ft | 222 ft | 148 ft | 111 ft | 89 ft | - |
| 4 | 472 ft | 354 ft | 236 ft | 177 ft | 141 ft | - |
| 3 | 595 ft | 446 ft | 297 ft | 223 ft | 178 ft | - |
| 2 | 750 ft | 562 ft | 375 ft | 281 ft | 224 ft | - |
| 1 | 960 ft | 719 ft | 480 ft | 359 ft | 288 ft | 144 ft |
| 1/0 | 1200 ft | 899 ft | 600 ft | 449 ft | 359 ft | 179 ft |
| 2/0 | 1500 ft | 1125 ft | 750 ft | 562 ft | 449 ft | 224 ft |
| 3/0 | 1846 ft | 1384 ft | 923 ft | 692 ft | 553 ft | 276 ft |
| 4/0 | 2400 ft | 1799 ft | 1200 ft | 899 ft | 719 ft | 359 ft |
Method and NEC reference
Distances are derived from NEC 2020 Chapter 9 conductor data: the K-factor method below 2 AWG and Table 9 effective impedance at 2 AWG and larger, at unity power factor and the 75°C basis, single-phase (round-trip) circuits. The 3% figure is the branch-circuit recommendation in the informational notes to NEC 210.19(A)(1); with feeder and branch combined, the recommendation is 5% (multiply distances by 5/3 ≈ 1.67 for a 5% budget). Voltage drop percentages scale linearly: a 240 V circuit allows exactly twice the distance of a 120 V circuit at the same current.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
How to read this chart
Find your load current in the column headers, read down to your planned one-way distance, and use the first conductor size whose distance meets or exceeds yours. Example: a 20 A load run 120 ft one-way at 120 V; 12 AWG allows less than that, so move to 10 AWG. Distances assume the entire load at the end of the run; distributed loads (a string of receptacles) see less drop than the chart implies, so the chart errs conservative.
The chart cannot see your ambient temperature, conduit fill, or termination ratings; those affect ampacity, not voltage drop, and can require a larger conductor than the chart shows. The Wire Size Calculator checks both constraints together.
Related tools
- Voltage Drop Calculator: exact drop for any voltage, current, size, and distance.
- 3-Phase Voltage Drop Calculator: 208/480 V three-phase circuits (√3 factor).
- DC Voltage Drop Calculator: solar, battery, and telecom DC circuits.
- Wire Size Calculator: ampacity and voltage drop in one answer.
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
For deeper NEC training on voltage drop and wire runs, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.