ElectricalToolbox

3-Phase Voltage Drop Calculator

Calculate line-to-line voltage drop on three-phase feeders and motor branch circuits. The long 480V runs and large 208V commercial feeders where drop actually drives conductor sizing. Results use NEC 2020 Chapter 9, Table 9 AC resistance for #2 AWG and larger, and the Table 8 K-factor for smaller conductors, at a 75°C basis and unity power factor.

Circuit inputs
Phase
Three-phase · line-to-line (√3)

Assumes PVC conduit, unity power factor (resistive load), and NEC Chapter 9 Table 9 conductor values at 75°C. Three-phase drop uses the √3 line-to-line factor.

How to use this calculator

  1. Select the line-to-line system voltage (480V, 208V, 240V, or 600V).
  2. Enter the load current in amps and the conductor material.
  3. Select the conductor size (AWG or kcmil).
  4. Enter the one-way distance from source to load in feet.
  5. Read total voltage drop, percentage, and the 3% / 5% status. If it exceeds 3%, the tool recommends the next conductor size that brings it back under 3%.

NEC reference

Three-phase voltage drop is calculated as VD = √3 × R × I × L ÷ 1000, where R is the AC resistance in ohms per 1000 ft from NEC Chapter 9, Table 9 (NEC 2020) for #2 AWG and larger, or the Table 8 K-factor for smaller conductors. The 3% branch-circuit and 5% combined feeder-plus-branch figures come from the informational notes to NEC 210.19 and 215.2. They are recommendations, not requirements, unless adopted locally.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

Three-phase voltage drop formula

Three-phase drop uses the same resistance basis as single-phase but a different multiplier, because current flows on three conductors 120° apart rather than out-and-back on two:

Three-phase: VD = √3 × R × I × L / 1000

Single-phase:  VD = 2 × R × I × L / 1000

R is resistance in ohms per 1000 ft, I is line current in amps, and L is the one-way distance in feet. √3 (≈1.732) replaces the 2× round-trip factor used on single-phase, which works out to three-phase drop being about 86.6% (√3/2) of single-phase drop for the same conductor, current, and length. For conductors below #2 AWG, R comes from the K-factor (R = K × 1000 / circular mils); for #2 and larger it comes directly from NEC Chapter 9 Table 9.

Worked example

A 60A three-phase feeder on #6 copper, 208V, 150 feet one way:

# 6 copper is smaller than #2 → K-factor, K = 12.9

R = 12.9 × 1000 / 26,240 cmil = 0.4916 Ω/1000 ft

VD = √3 × (0.4916 / 1000) × 60 × 150 = 7.66 V

VD% = 7.66 / 208 = 3.68%

At 3.68% this exceeds the NEC 210.19 branch-circuit recommendation of 3%. It's acceptable only as part of a combined feeder-plus-branch budget under NEC 215.2. Stepping up to #4 copper brings it back under the 3% branch recommendation.

Common mistakes

  • Using the single-phase 2× factor by mistake. Three-phase uses √3 (≈1.732), not 2. Using the wrong factor overstates drop by about 15%. Enough to reject a conductor that actually passes.
  • Entering line-to-neutral instead of line-to-line voltage. Three-phase feeder and motor circuits are sized against the line-to-line (phase-to-phase) voltage (480V, 208V, or 600V), not the 277V or 120V line-to-neutral voltage that single-phase loads on the same system use.
  • One-way vs round-trip distance. Enter the one-way run length. The calculator applies the √3 multiplier internally. Entering the there-and-back length double-counts the conductor.
  • Ignoring motor power factor. This calculator assumes unity power factor. Motors run at a lagging power factor, which increases real-world drop beyond what this tool reports. Treat the result as a floor for motor branch circuits, not a guarantee.

Frequently asked questions

Why does three-phase use √3 instead of 2 like single-phase?

Single-phase voltage drop uses a factor of 2 because current travels out on one conductor and back on another. A full round trip. Three-phase circuits have three current-carrying conductors 120° apart, and the line-to-line voltage relationship between any two of them works out to √3 (about 1.732) times the phase resistance drop rather than 2×. The result is that three-phase drop is about 86.6% (√3/2) of what the same conductor, current, and length would show on single-phase.

Should I enter line-to-line or line-to-neutral voltage?

Enter the line-to-line (phase-to-phase) system voltage. 480V, 208V, or 600V for typical commercial and industrial services. This calculator computes drop across the line-to-line voltage, which is the standard basis for three-phase feeder and motor circuit design. Line-to-neutral voltage (277V, 120V) is a different calculation and applies to single-phase loads fed from a three-phase system, not to the three-phase circuit itself.

Does the NEC require voltage drop calculations on three-phase feeders?

No. The 3% branch-circuit and 5% combined feeder-plus-branch figures are informational notes in NEC 210.19(A)(1) and 215.2(A)(1). Recommendations, not enforceable requirements, unless a local jurisdiction adopts them by amendment. That said, three-phase feeders are exactly where voltage drop tends to matter most in practice: they carry the highest currents over the longest runs in a building, and motors are sensitive to under-voltage at the terminals.

What's an acceptable voltage drop for a three-phase motor feeder?

NEC 430 does not set a voltage-drop figure, but motors are unusually sensitive to it: starting torque falls with the square of terminal voltage, and low voltage raises running current and heat. Many engineering specs hold motor feeders to 3% and total system drop to 5%, tighter than the NEC informational-note baseline. This calculator assumes unity power factor; motors run at a lagging power factor, which increases real-world drop, so treat the result as a floor, not a ceiling, for motor work.

Why is my three-phase result lower than a single-phase calculator gave me for the same load?

That's expected, not an error. It's the √3 vs. 2 factor described above. For identical voltage, current, conductor, and distance, three-phase drop is always about 86.6% of single-phase drop. If you're comparing a real single-phase branch to a real three-phase feeder, the two aren't equivalent circuits anyway. Check that you're using this tool for the actual three-phase load, not spot-checking against a different circuit type.

When does three-phase voltage drop matter most?

Long feeder runs, high current, and undersized conductors. The same drivers as single-phase, but three-phase feeders typically carry more current over longer distances (service entrances, panel feeders, large motor branches), so the absolute drop can be significant even though the √3 factor is smaller than single-phase's 2×. Watch it closely on 208V systems especially, since the lower system voltage means the same volt-drop is a larger percentage than on 480V.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

For deeper NEC training on three-phase feeder and motor circuit sizing, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.