Grounding and Bonding Practice Test

Twenty questions on National Electrical Code (NEC) Article 250: the grounding electrode system and permitted electrodes, what must be bonded, the main, system, and equipment bonding jumpers, grounded-conductor rules at services versus downstream, separately derived systems, and equipment grounding conductor types and sizing. Weighted toward rule and concept questions, with a few worked sizing problems linked to the calculator that solves each.

Question 1

Question 1 of 20 · Grounding vs bonding

In NEC Article 100, 'bonded (bonding)' is defined as:

Question 2

Question 2 of 20 · Grounding electrode system

A building has a metal underground water pipe, a concrete-encased electrode, and a ground rod all present. Under NEC 250.50 the installer must:

Question 3

Question 3 of 20 · Grounding electrodes

A single ground rod is measured and does not have a resistance to earth of 25 ohms or less. NEC 250.53(A)(2) requires that the rod:

Question 4

Question 4 of 20 · Grounding electrodes

A rod electrode must have at least how much length in contact with the soil (NEC 250.52(A)(5) and 250.53(G))?

Question 5

Question 5 of 20 · Grounding electrodes

A metal underground water pipe qualifies as a grounding electrode only where it is in direct contact with the earth for at least (NEC 250.52(A)(1)):

Question 6

Question 6 of 20 · Equipment grounding conductor

A 20 A circuit would normally use 12 AWG copper conductors with a 12 AWG copper equipment grounding conductor, but the ungrounded conductors are increased to 8 AWG copper for voltage drop. Per NEC 250.122(B) the equipment grounding conductor must be increased to:

Check this with the Equipment Grounding Conductor Size Calculator.

Question 7

Question 7 of 20 · Equipment grounding conductor

A 400 A feeder is run as two conductors per phase in two parallel metal raceways. Per NEC 250.122(F), the copper equipment grounding conductor in EACH raceway (Table 250.122, 400 A) is:

Check this with the Equipment Grounding Conductor Size Calculator.

Question 8

Question 8 of 20 · Bonding requirements

NEC 250.94 requires that an accessible means external to enclosures be provided at the service for connecting:

Question 9

Question 9 of 20 · Bonding jumpers

The main bonding jumper (NEC 250.24(B) and 250.28) connects the:

Question 10

Question 10 of 20 · Grounded conductor rules

On the load side of the service disconnecting means, the grounded (neutral) conductor (NEC 250.142(B)) shall generally:

Question 11

Question 11 of 20 · Grounded conductor rules

A 4-wire feeder supplies a detached garage from the main building. Per NEC 250.32(B), the grounding at the garage must:

Question 12

Question 12 of 20 · Separately derived systems

At the source (or first disconnect) of a separately derived system such as a transformer secondary, NEC 250.30(A)(1) requires a:

Question 13

Question 13 of 20 · Bonding jumpers

A separately derived system has 500 kcmil copper phase conductors. The copper system bonding jumper sized from NEC Table 250.102(C)(1) is:

Question 14

Question 14 of 20 · Bonding jumpers

A service is supplied by 600 kcmil aluminum ungrounded conductors. The aluminum supply-side bonding jumper sized from NEC Table 250.102(C)(1) is:

Question 15

Question 15 of 20 · Bonding requirements

A service has 700 kcmil copper ungrounded conductors. The copper bonding jumper for the metal water piping system, sized per NEC 250.104(A)(1) from Table 250.66, is:

Check this with the Grounding Electrode Conductor Size Calculator.

Question 16

Question 16 of 20 · Grounding electrode conductor

A service uses two 3/0 AWG copper conductors in parallel per phase. The copper grounding electrode conductor from NEC Table 250.66 (using the combined area) is:

Check this with the Grounding Electrode Conductor Size Calculator.

Question 17

Question 17 of 20 · Equipment grounding conductor

Which of the following is recognized by NEC 250.118 as an equipment grounding conductor?

Question 18

Question 18 of 20 · Equipment grounding conductor

An insulated equipment grounding conductor is identified by (NEC 250.119):

Question 19

Question 19 of 20 · Bonding requirements

Metal raceways and enclosures containing service conductors must be bonded by one of the specific methods in NEC 250.92(B) because:

Question 20

Question 20 of 20 · Bonding requirements

Exposed structural metal that is interconnected to form a metal building frame and is likely to become energized must, per NEC 250.104(C):

How to use this practice test

  1. Answer each of the 20 questions, working the sizing problems by hand from the cited Article 250 table.
  2. On the calculated questions, use the linked calculator to check your table lookup before you grade.
  3. Grade the test. Each question reveals the explanation and its exact NEC section or table.
  4. For any miss, open the cited section and read the rule. Grounding and bonding is a navigation exam as much as a knowledge one.

NEC reference

Questions reference the NEC 2020 edition, NEC Article 250. Answers follow NEC Article 250. The Article 250 section numbering used here (250.30, 250.50, 250.52, 250.53, 250.92, 250.94, 250.102, 250.104, 250.118, 250.119, 250.122, 250.142) and the values in Tables 250.66, 250.102(C)(1), and 250.122 are unchanged across the 2017, 2020, and 2023 editions. Conductor circular-mil areas come from NEC Chapter 9 Table 8. Table 250.102(C)(1) and Table 250.66 share the same conductor sizes for phase conductors up to 1100 kcmil copper / 1750 kcmil aluminum; they diverge only above that range, where 250.102(C)(1) switches to the 12.5% rule. Every calculated answer is verified against the same National Electrical Code table data that powers this site's calculators: Table 250.66 (grounding electrode conductor), Table 250.122 (equipment grounding conductor), Table 250.102(C)(1) (bonding jumpers), and Chapter 9 Table 8 (conductor circular mils).

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

Continuing education and exam prep

Many licensing jurisdictions require continuing education hours each renewal cycle. Mike Holt's continuing education courses are organized by state, and his exam preparation programs cover journeyman and master license exams. Confirm any course is approved for your license and jurisdiction before enrolling.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.

Check your work with the calculators

The calculated questions above link the grounding and bonding calculators that solve them:

The main, system, and supply-side bonding jumper questions size from Table 250.102(C)(1), which has no dedicated calculator yet; those values are worked by hand in each explanation.

Want the full exam format? The journeyman practice test and master practice test mix grounding with the rest of the code, and the electrical calculations practice test drills the math. Working in a specific state? Confirm which NEC edition your state enforces. Your exam references the adopted edition.