ElectricalToolbox

Electrical Calculations Practice Test

Twenty questions on the National Electrical Code (NEC) calculations, almost every one a worked problem: voltage drop, conduit and box fill, ampacity and derating, conductor and overcurrent sizing, grounding conductors, and transformer sizing. Graded instantly, with the arithmetic shown and the governing table cited. Each calculated question links the calculator that solves it.

Question 1

Question 1 of 20 · Voltage drop

A 240 V single-phase branch circuit carries 24 A over a 150 ft one-way run in 10 AWG copper. Using the K-factor method (K = 12.9 for copper, 10 AWG = 10,380 cmil), the approximate voltage drop is:

Check this with the Voltage Drop Calculator.

Question 2

Question 2 of 20 · Voltage drop

A 208 V three-phase feeder carries 100 A over a 250 ft one-way run in 1/0 AWG copper (Chapter 9 Table 9 AC resistance, 0.12 ohm per 1000 ft). The approximate voltage drop is:

Check this with the 3 Phase Voltage Drop Calculator.

Question 3

Question 3 of 20 · Voltage drop

A 120 V single-phase circuit carries 16 A over a 100 ft one-way run in 12 AWG copper (K = 12.9, 12 AWG = 6,530 cmil). The voltage drop as a percentage of source voltage is closest to:

Check this with the Voltage Drop Calculator.

Question 4

Question 4 of 20 · Conduit fill

Nine 8 AWG THHN conductors (0.0366 in² each, Chapter 9 Table 5) are pulled through EMT. Using the Chapter 9 Table 1 fill limit for more than two conductors, the minimum EMT trade size is:

Check this with the Conduit Fill Calculator.

Question 5

Question 5 of 20 · Conduit fill

Per NEC Chapter 9, Table 1, the maximum conduit fill for a raceway containing more than two conductors (not a nipple) is:

Question 6

Question 6 of 20 · Box fill

A device box holds six 14 AWG conductors, one duplex receptacle (one yoke), internal cable clamps, and the equipment grounding conductors. Using the Table 314.16(B) allowances (14 AWG = 2.00 in³), the minimum box volume is:

Check this with the Box Fill Calculator.

Question 7

Question 7 of 20 · Ampacity and derating

Six current-carrying 8 AWG THHN copper conductors (90°C rated, 75°C terminations) share a raceway at 30°C ambient. After the more-than-three-conductor adjustment, the usable ampacity is:

Check this with the Wire Ampacity Calculator.

Question 8

Question 8 of 20 · Ampacity and derating

A 4 AWG THWN copper conductor (75°C, base ampacity 85 A) runs through an area at 43°C ambient with three current-carrying conductors. After ambient correction, its ampacity is:

Check this with the Ampacity Correction Calculator.

Question 9

Question 9 of 20 · Ampacity and derating

Reading NEC Table 310.16 at the 75°C column, the allowable ampacity of 4/0 AWG aluminum (three or fewer current-carrying conductors, 30°C ambient) is:

Check this with the Wire Ampacity Calculator.

Question 10

Question 10 of 20 · Conductor sizing

A 60 A noncontinuous load is served by copper conductors with 75°C terminations at 30°C ambient (three current-carrying conductors). The minimum copper branch-circuit conductor from NEC Table 310.16 is:

Check this with the Wire Size Calculator.

Question 11

Question 11 of 20 · Overcurrent protection

A continuously operating general-use load draws 44 A. The minimum standard circuit breaker per NEC 210.20(A) and 240.6(A) is:

Check this with the Breaker Size Calculator.

Question 12

Question 12 of 20 · Overcurrent protection

A continuous general-use load draws 80 A. The minimum standard fuse per NEC 210.20(A) and 240.6(A) is:

Check this with the Fuse Size Calculator.

Question 13

Question 13 of 20 · Grounding and bonding

A feeder is protected by a 200 A overcurrent device. The minimum copper equipment grounding conductor from NEC Table 250.122 is:

Check this with the Equipment Grounding Conductor Size Calculator.

Question 14

Question 14 of 20 · Grounding and bonding

A service is supplied by 3/0 AWG copper service-entrance conductors. The minimum copper grounding electrode conductor from NEC Table 250.66 is:

Check this with the Grounding Electrode Conductor Size Calculator.

Question 15

Question 15 of 20 · Transformer sizing

A 30 kVA, three-phase transformer has a 480 V primary and primary-only overcurrent protection. Per NEC Table 450.3(B), the maximum primary circuit breaker is:

Check this with the Transformer Sizing Calculator.

Question 16

Question 16 of 20 · Service and feeder load

A single 14 kW household electric range is served by an individual branch circuit. Its demand load, using NEC Table 220.55 Column C with Note 1, is:

Check this with the Residential Electrical Load Calculator.

Question 17

Question 17 of 20 · Service and feeder load

Using the optional dwelling calculation (NEC 220.82), a general load of 30 kVA is figured at 100% of the first 10 kVA and 40% of the remainder. The general-load demand (before adding heating or air-conditioning) is:

Check this with the Electrical Load Calculator.

Question 18

Question 18 of 20 · Overcurrent protection

Regardless of its calculated ampacity, the maximum standard overcurrent protection for a 12 AWG copper conductor under the small-conductor rule is:

Question 19

Question 19 of 20 · Overcurrent protection

Before any ampacity adjustment, the conductors and overcurrent device for a continuous load must be sized for not less than ______ of that continuous load.

Question 20

Question 20 of 20 · Grounding and bonding

Where a grounding electrode conductor connects solely to a rod, pipe, or plate electrode, NEC 250.66(A) says it need not be larger than:

How to use this practice test

  1. Work each of the 20 problems by hand first. Treat the calculations as open-book, the way exam time pressure actually plays out.
  2. Use the calculator linked under each question to check your own arithmetic and table lookup before you grade.
  3. Grade the test. Each question reveals the worked answer and its NEC reference.
  4. For any miss, look up the cited table and re-derive the answer yourself. Fast, confident navigation to the reference is most of the exam skill.

NEC reference

Questions reference the NEC 2020 edition. Answers use values identical across the 2017, 2020, and 2023 editions unless the explanation says otherwise. Chapter 9 Tables 1, 4, 5, 8, and 9, Table 310.16, Table 314.16(B), Table 250.66, Table 250.122, Table 450.3(B), Table 220.55 Column C, and the 240.6(A) standard ratings are unchanged across those editions. Section numbering follows the 2020/2023 editions; in NEC 2017, Table 310.16 was 310.15(B)(16) and Table 310.15(C)(1) was 310.15(B)(3)(a). Every calculated answer in this set is verified against the same National Electrical Code table data that powers this site's calculators. Chapter 9 Tables 1, 4, 5, 8, and 9, Table 310.16, Tables 310.15(B)(1) and 310.15(C)(1), Table 314.16(B), Table 250.66, Table 250.122, Table 450.3(B), Table 220.55, and the 240.6(A) standard ratings.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

Continuing education and exam prep

Many licensing jurisdictions require continuing education hours each renewal cycle. Mike Holt's continuing education courses are organized by state, and his exam preparation programs cover journeyman and master license exams. Confirm any course is approved for your license and jurisdiction before enrolling.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.

Check your work with the calculators

Every calculated question above links the calculator that solves it. The full set covering this test:

Want the full exam format? The journeyman practice test and master practice test mix these calculations with the rule questions. Working in a specific state? Confirm which NEC edition your state enforces. Your exam references the adopted edition.