Pull Box Size Calculator

Size a pull box, junction box, or conduit body to NEC 314.28(A) from the raceway trade sizes and the pull geometry. Straight pulls take 8 times the largest raceway; angle and U pulls take 6 times the largest in a row plus the sum of the other raceways on that wall. Default NEC 2020 (multipliers unchanged 2017 to 2023).

Pull type

Use this only where the box contains conductors 4 AWG and larger. For boxes whose conductors are all 6 AWG and smaller, use the Box Fill Calculator (314.16).

Straight-pull raceways

Add every raceway making the straight pull. Only the largest one sets the box length.

How to use this calculator

  1. Choose the pull type: a straight pull (raceways entering one wall and leaving the directly opposite wall) or an angle/U pull (raceways turning to a different wall, or splices in the box).
  2. For a straight pull, add the raceways making the pull. For an angle/U pull, add each wall that receives entries and list the raceway trade sizes entering that wall.
  3. Read the minimum dimension for each wall or pull. For an angle pull, also read the same-conductor distance, the minimum straight-line spacing between the entering and leaving raceway of one conductor.
  4. Build or select a box that meets every listed dimension. Remember this is only for boxes with conductors 4 AWG and larger; smaller conductors use box fill (314.16).

NEC reference

Dimensions are computed per NEC 2020 Article 314.28(A). Straight pulls follow 314.28(A)(1): the box length is at least 8 times the trade size of the largest raceway. Angle pulls, U pulls, and splices follow 314.28(A)(2): the distance from each raceway entry to the opposite wall is at least 6 times the largest raceway in that row, increased by the sum of the trade sizes of the other raceways in the same row on the same wall, and the distance between raceway entries enclosing the same conductor is at least 6 times the larger of the two. The 8x and 6x multipliers are unchanged across the 2017, 2020, and 2023 editions. Article 314.28 applies to boxes and conduit bodies containing conductors 4 AWG and larger.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

The two NEC 314.28(A) rules

Pull type Minimum dimension NEC
Straight pull 8 × largest raceway trade size 314.28(A)(1)
Angle / U pull, splice (wall to opposite wall) 6 × largest in row + sum of other raceways in the row 314.28(A)(2)
Same conductor (entry to its exit raceway) 6 × larger of the two raceways 314.28(A)(2)

Trade size (metric designator) is used in inches directly, so a 3" conduit contributes 3 to the multiplier. Article 314.28 applies only once a box carries conductors 4 AWG or larger; boxes whose conductors are all 6 AWG and smaller are sized by 314.16(B) box fill instead.

Worked example: an angle pull with three conduits

Conductors enter the left wall of a junction box through one 3" and two 2" conduits and turn 90 degrees to leave the bottom wall through matching raceways.

  • Left wall (angle pull): 6 × 3 + 2 + 2 = 22 in to the opposite wall (314.28(A)(2)).
  • Bottom wall (angle pull): the same three raceways give 6 × 3 + 2 + 2 = 22 in.
  • Same conductor: the entering and leaving raceway of one conductor must be at least 6 × 3 = 18 in apart.

So the box must be at least 22 in × 22 in in the plane of the pulls, and the corner-to-corner geometry must keep paired raceways 18 in apart. Compare that to a straight pull of the same 3" conduit, which needs only 8 × 3 = 24 in of length and no minimum width from 314.28: the 90 degree turn is what drives the box larger, because conductors need room to make the bend without damage.

Details that trip people up

  1. Straight pulls use only the largest raceway. Four 2" conduits in a straight pull still need just 8 × 2 = 16 in; the other three do not add. Angle pulls are the opposite: the other raceways in the row do add.
  2. Each wall is its own row. Calculate every wall that receives entries separately and take each result as that box dimension. The single row giving the largest distance governs its axis.
  3. Trade size, not conductor count. 314.28 never looks at how many wires are in the pipe; Chapter 9 conduit fill already limits that. Only the raceway trade sizes and the geometry matter here.
  4. Removable-cover reduction is not applied here. Where a raceway enters directly opposite a removable cover, 314.28(A)(2) Exception lets the wall-to-cover distance follow the Table 312.6(A) bending space instead of 6x. This calculator reports the full 6x distance, which is always compliant.

Frequently asked questions

What is the difference between a pull box and a junction box?

A pull box gives conductors a place to be pulled through a long or complex raceway run without splices; a junction box holds splices or taps. NEC 314.28(A) sizes both the same way from the raceway trade sizes, and the angle/U-pull rule explicitly covers boxes that contain splices.

Why is an angle pull box bigger than a straight pull box?

Conductors 4 AWG and larger are stiff and cannot bend sharply without damaging the insulation. A straight pull only needs enough length to feed the conductors through (8x), but an angle pull needs room across the box for the conductor to make the turn (6x from each entry to the far wall, plus the other raceways), which usually produces a larger box.

Does 314.28 set the box depth?

314.28(A) sets the in-plane dimensions from the pulls. Depth is driven by the raceway entries and fittings on the back or sides and by conductor bending space; a box deep enough to land the locknuts and bushings and clear the conductors satisfies the pull geometry. This tool reports the pull dimensions the 8x and 6x rules require.

What conductors require 314.28 sizing?

Any box or conduit body containing conductors 4 AWG or larger. Below that, through 6 AWG and smaller, boxes are sized by the 314.16(B) volume box-fill method. Feeder and service pulls almost always land in 314.28 territory.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

For deeper NEC training on pull boxes, junction boxes, and raceway rough-in, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.