Receptacle Replacement Requirement Calculator
Find out what a replacement receptacle has to be under the National Electrical Code (NEC). Answer whether the box has an equipment grounding conductor and whether the location now requires GFCI, AFCI, tamper-resistant, or weather-resistant protection, and the tool applies NEC 2020 406.4(D), including the two-prong, no-ground case and its three permitted options.
How to use this calculator
- Say whether an equipment grounding conductor is present in the box. That sets the 406.4(D)(1) grounding-type path or the 406.4(D)(2) no-ground options.
- Pick whether the receptacle you are removing is a grounding (three-prong) or nongrounding (two-prong) type. This drives the tamper-resistant relief in 406.4(D)(5).
- For each protection, say whether the location requires it now: GFCI (210.8), AFCI (210.12), tamper-resistant (406.12), weather-resistant (406.9). Use the linked tools if you are not sure.
- Read the verdict: the required device for the grounding path, the three options when there is no ground, and which protections carry onto the replacement.
- Resolve anything flagged for review before you rely on the result; an unknown condition is never treated as "not required."
NEC reference
This calculator implements NEC 2020 406.4(D), Replacements. 406.4(D)(1) covers a box with a grounding means; 406.4(D)(2) covers a box with none and lists the three permitted options; 406.4(D)(3) and 406.4(D)(4) carry GFCI (210.8) and AFCI (210.12) protection onto the replacement where the location requires them; 406.4(D)(5) and 406.4(D)(6) do the same for tamper-resistant (406.12) and weather-resistant (406.9) receptacles. Whether a location requires each protection is handled by separate tools.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
The grounding question comes first (406.4(D)(1) and (D)(2))
The single branch that decides a receptacle replacement is whether the outlet box has an equipment grounding conductor. With one, the replacement is a grounding-type receptacle and its grounding terminal is connected to that conductor (406.4(D)(1)). With none, which is the common situation in older two-wire wiring, the replacement must be one of three options.
| No-ground option | Required marking | NEC |
|---|---|---|
| Nongrounding (two-prong) receptacle | None | 406.4(D)(2)(a) |
| GFCI-type receptacle | "No Equipment Ground" | 406.4(D)(2)(b) |
| Grounding-type receptacle fed downstream of a GFCI | "GFCI Protected" and "No Equipment Ground" | 406.4(D)(2)(c) |
When a GFCI is used for a no-ground replacement, an equipment grounding conductor must not be run from it to any outlet it supplies (406.4(D)(2)(b)). The device is protecting against ground faults without a real ground path, so the markings warn the next person that the three-prong opening does not mean an equipment ground is present.
The protections carry onto the replacement (406.4(D)(3) through (D)(6))
406.4(D) has no grandfathering. If the location requires a protection under the currently adopted Code, the replacement device has to provide it, even when the receptacle you are removing predated the rule. These four requirements are independent and stack on top of the grounding answer.
| Protection | Triggered by | NEC |
|---|---|---|
| GFCI protection | Location requires GFCI (210.8) | 406.4(D)(3) |
| AFCI protection | Location requires AFCI (210.12) | 406.4(D)(4) |
| Tamper-resistant | Location requires TR (406.12) | 406.4(D)(5) |
| Weather-resistant | Damp or wet location (406.9) | 406.4(D)(6) |
The one relief is in 406.4(D)(5): a nongrounding receptacle replaced with another nongrounding receptacle does not have to be tamper-resistant. As soon as you upgrade to a grounding-type or GFCI-type device at a tamper-resistant location, the tamper-resistant requirement applies again.
Worked example: a kitchen counter receptacle
You are replacing a worn receptacle above a kitchen counter. The box has an equipment grounding conductor, so 406.4(D)(1) requires a grounding-type receptacle connected to it. A kitchen counter outlet is a 210.8(A) GFCI location, so 406.4(D)(3) requires the replacement to be GFCI-protected, and because it is a dwelling, 406.4(D)(5) requires it to be tamper-resistant. The correct device is a listed tamper-resistant GFCI receptacle (or a tamper-resistant receptacle on a GFCI-protected circuit). Move the same job to a 1960s bedroom with two-wire cable and no ground, and the answer changes to the 406.4(D)(2) options: a two-prong replacement, a GFCI marked "No Equipment Ground," or a grounding-type downstream of a GFCI marked "GFCI Protected" and "No Equipment Ground," with AFCI protection added per 406.4(D)(4) if the bedroom circuit requires it.
Common mistakes
- Assuming a straight swap carries no new requirements. There is no grandfathering under 406.4(D); the replacement must meet the current rule for the location.
- Putting a three-prong receptacle on an ungrounded box with nothing else. With no equipment ground, a grounding-type device is only permitted downstream of a GFCI and marked accordingly (406.4(D)(2)(c)).
- Running a ground wire from a no-ground GFCI to its downstream outlets. 406.4(D)(2)(b) prohibits it; the GFCI is the protection, not a real ground.
- Skipping the "No Equipment Ground" marking. It is required on the no-ground GFCI options so the next person is not misled by the three-prong face.
- Forgetting tamper-resistant on a grounding-type upgrade. The TR relief is only for a nongrounding-to-nongrounding swap.
Frequently asked questions
Do I need a GFCI to replace an outlet?
Under NEC 406.4(D)(3), you must provide GFCI protection on the replacement if the outlet is at a location that the currently adopted Code requires to be GFCI-protected (210.8), for example a kitchen, bathroom, garage, or outdoor receptacle, even if the original device was not GFCI-protected. Where the location does not require GFCI protection, a replacement does not have to be GFCI just because you are swapping the device. Separately, if there is no equipment grounding conductor in the box, 406.4(D)(2)(b) lets you use a GFCI-type receptacle marked "No Equipment Ground" as one way to replace a two-prong receptacle.
Can I replace a two-prong receptacle with a three-prong one?
Only with a path to ground or with GFCI protection. If the box has an equipment grounding conductor, 406.4(D)(1) requires a grounding-type (three-prong) receptacle connected to it. If the box has no equipment grounding conductor, NEC 406.4(D)(2) gives three options: a nongrounding (two-prong) replacement; a GFCI-type receptacle marked "No Equipment Ground"; or a grounding-type receptacle fed downstream of a GFCI and marked "GFCI Protected" and "No Equipment Ground."
Does a replacement receptacle have to be tamper-resistant?
NEC 406.4(D)(5) requires a listed tamper-resistant receptacle wherever a replacement is made at an outlet that is required to be tamper-resistant under 406.12, such as in a dwelling unit. The one relief is a nongrounding receptacle replaced with another nongrounding receptacle, which does not have to be tamper-resistant. Upgrading to a grounding-type or GFCI-type device at a tamper-resistant location brings the requirement back.
Is there grandfathering when I replace a receptacle?
No. NEC 406.4(D) requires a replacement receptacle to meet the protection that applies to its location under the currently adopted Code, even when the original device predated that rule. Swapping the receptacle is the trigger: GFCI (210.8), AFCI (210.12), tamper-resistant (406.12), and weather-resistant (406.9) requirements all attach to the new device where the location calls for them.
What must an AFCI replacement receptacle be?
NEC 406.4(D)(4) requires arc-fault protection on a replacement where the location is required to be AFCI-protected under 210.12. It is satisfied by a listed outlet branch-circuit (OBC) type AFCI receptacle, a receptacle installed downstream of a listed OBC AFCI receptacle, or a receptacle protected by a listed combination-type AFCI circuit breaker. Limited exceptions exist in the Code; confirm them against the adopted edition before relying on one.
Related calculators
- GFCI Breaker Sizing Calculator: where dwelling and non-dwelling receptacles need ground-fault protection per NEC 210.8.
- AFCI Requirement & Breaker Sizing Calculator: where dwelling branch circuits need arc-fault protection per NEC 210.12.
- Tamper-Resistant & Weather-Resistant Receptacle Calculator: where a receptacle must be TR or WR per NEC 406.12 and 406.9.
- Dwelling Receptacle Spacing Calculator: the 210.52 wall and countertop receptacle placement rules.
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.
For deeper NEC training on receptacle device selection and code compliance, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.
Get new tools and reference cards by email
Occasional emails when a new calculator, guide, or printable card ships. No spam, unsubscribe anytime.