Transformer Secondary Conductor Calculator

Size a transformer secondary conductor under the NEC 240.21(C) secondary conductor rules. Enter the primary overcurrent device, the primary and secondary voltages, and the secondary run length; the tool figures the reflected primary OCPD, applies the 10-foot rule (240.21(C)(2)), the 25-foot rule (240.21(C)(6)), or the primary-only option (240.21(C)(1)), and returns the smallest copper or aluminum conductor from Table 310.16.

Transformer

25-ft rule (240.21(C)(6))

Conductor

Defaults (75 °C termination, 86 °F ambient, 3 conductors) match the published base examples. Enter real conditions to derate per Table 310.15.

How to use this calculator

  1. Enter the rating of the overcurrent device protecting the transformer primary.
  2. Enter the primary and secondary voltages and the secondary configuration. The tool computes the reflected primary OCPD from the voltage ratio.
  3. Enter the secondary length. The tool selects the 10-foot, 25-foot, or primary-only rule automatically and shows which one governs.
  4. On the 10-foot path, enter the rating of the single device the secondary terminates in and whether the conductors leave the enclosure (which adds the one-tenth-of-reflected floor).
  5. Pick the conductor material and termination temperature column, and adjust ambient temperature or conductor count if your install is not at the base conditions.
  6. Read the required ampacity, the smallest qualifying conductor, and the remaining code conditions you still have to meet.

NEC reference

This calculator follows NEC 2020 Section 240.21(C). The 10-foot rule is 240.21(C)(2): the secondary ampacity must equal the calculated load and the device at its termination, and where the conductors leave the enclosure the reflected primary device may not exceed 10 times the secondary ampacity. The 25-foot rule is 240.21(C)(6): the secondary ampacity must be at least one-third of the reflected primary overcurrent device and the conductors must terminate in a single overcurrent device. The primary-only option is 240.21(C)(1), available for a single-phase two-wire or delta-delta three-wire secondary sized to the full reflected OCPD. Conductor ampacity comes from Table 310.16, with Table 310.15(B)(1) ambient correction and Table 310.15(C)(1) adjustment when you enter non-base conditions. The rule text and the 1/10 and 1/3 fractions are identical across the 2017, 2020, and 2023 editions.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

Why a transformer secondary is not a feeder tap

A feeder tap connects to a feeder at the same voltage, so its ampacity is a fraction of the feeder overcurrent device directly. A transformer secondary conductor is different: a transformer sits between the primary overcurrent device and the conductor, and it changes the current. Because a transformer conserves apparent power, the secondary current is the primary current scaled by the primary-to-secondary voltage ratio. The primary overcurrent device therefore reflects onto the secondary as a different number, and every 240.21(C) secondary ampacity is a fraction of that reflected value, not of the primary rating itself.

Reflected primary OCPD = primary device rating times the primary voltage divided by the secondary voltage. For a step-down transformer the reflected value is larger than the primary rating, because the secondary current is higher. Swapping the two voltages inverts the ratio and undersizes the conductor badly, which is the most common mistake in these calculations.

The three secondary rules

240.21(C)(1) lets the primary overcurrent device protect the secondary at any length, but only for a single-phase two-wire or three-phase delta-delta three-wire secondary, and only when the conductor is sized to the full reflected OCPD. 240.21(C)(2) is the 10-foot secondary rule: the conductor ampacity has to at least match the single device it feeds, and where it leaves the enclosure it also has to be at least one-tenth of the reflected OCPD. 240.21(C)(6) is the 25-foot secondary rule: it trades a larger minimum ampacity, one-third of the reflected OCPD, for the longer allowable run, and requires the conductors to land on a single breaker or fuse set.

Worked example: 75 kVA, 480 to 208 V, 25-foot secondary

  1. The transformer has a 125 A device on its 480 V primary and a 208Y/120 V secondary that runs 25 feet, so the 25-foot rule applies.
  2. Reflected primary OCPD is 125 times 480 divided by 208, which is 288.5 A.
  3. Required secondary ampacity is one-third of that: 288.5 / 3 = 96.2 A.
  4. In the 75 degrees C column of Table 310.16, 4 AWG copper is 85 A, which falls short of 96.2 A.
  5. 3 AWG copper is 100 A, which meets it, so the minimum secondary conductor is 3 AWG copper.
  6. The secondary still has to terminate in a single device rated no more than 100 A and be protected from physical damage.

Why 240.4(D) does not limit a secondary conductor

For an ordinary branch conductor, 240.4(D) caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG, and 30 A for 10 AWG copper regardless of the table ampacity. Those caps do not apply to transformer secondary conductors: 240.4 makes an exception for conductors sized under 240.21, so a secondary conductor is sized on its full Table 310.16 ampacity. This calculator applies that exception and does not impose the 240.4(D) cap.

Conditions beyond ampacity

Meeting the ampacity fraction is necessary but not sufficient. The results panel lists the remaining conditions for the applied rule: for a 25-foot secondary, termination in a single overcurrent device and protection from physical damage; for a 10-foot secondary, not extending beyond the equipment supplied and, where it leaves the enclosure, the 10-times reflected-device limit. A conductor that meets the ampacity but fails a condition is not a compliant secondary.

Frequently asked questions

What is the 25-foot transformer secondary rule?

NEC 240.21(C)(6) allows a transformer secondary conductor up to 25 feet where the ampacity is at least one-third of the reflected primary overcurrent device, the conductors terminate in a single breaker or fuse set, and they are protected from physical damage.

How do I figure the reflected primary OCPD?

Multiply the primary overcurrent device rating by the primary voltage divided by the secondary voltage. A 125 A device on a 480 to 208 V transformer reflects to 125 times 480 divided by 208, or 288 A.

Does the primary breaker protect the secondary conductors?

Only for a single-phase two-wire or delta-delta three-wire secondary sized to the full reflected OCPD, under 240.21(C)(1). Other configurations need a 10-foot or 25-foot rule or a secondary overcurrent device.

Does NEC 240.4(D) apply to secondary conductors?

No. 240.4 excepts conductors sized under 240.21 from the small-conductor limits, so a secondary conductor is sized on its full table ampacity rather than the 15, 20, or 30 A caps for 14, 12, and 10 AWG copper.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.

For deeper NEC training on transformer secondary conductors and NEC 240.21 overcurrent protection, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.

Get new tools and reference cards by email

Occasional emails when a new calculator, guide, or printable card ships. No spam, unsubscribe anytime.