Continuous Load Calculator

Apply the NEC continuous-load rule in both directions. Enter a continuous and noncontinuous load to get the minimum overcurrent device and conductor ampacity (210.20(A), the 125% rule), or enter an existing breaker rating to find the maximum load it can carry (the 80% rule). No wire-size guesswork buried inside a bigger tool, just the rule itself.

What do you want to find?
Load on the circuit

How to use this calculator

  1. Choose a direction. "Size a circuit from a load" finds the minimum breaker and conductor; "Find an existing circuit's capacity" applies the 80% rule to a breaker you already have.
  2. Separate your load into continuous (running 3 hours or more) and noncontinuous amps. If your load is in volt-amps, switch the unit to VA and enter the voltage and phase to convert at unity power factor.
  3. Check the 100%-rated assembly box only if the equipment is listed for 100% continuous operation (usually 400 A and up). Leave it clear for ordinary breakers, which are 80% rated.
  4. Read the result. In size mode you get the minimum standard 240.6(A) device and the conductor ampacity to carry to the wire-size step; in capacity mode you get the maximum continuous and noncontinuous load, and the room left over when loads are already present.
  5. Take the conductor ampacity to the Wire Size or Wire Ampacity calculator to pick the actual AWG with your temperature and conductor-count conditions.

NEC reference

Sizing follows NEC 2020. Section 210.20(A) (branch circuits) and 215.3 (feeders) require the overcurrent device to be rated at not less than the noncontinuous load plus 125% of the continuous load. Sections 210.19(A)(1) and 215.2(A)(1) apply the same minimum to the conductor ampacity before any ambient-temperature or conductor-count adjustment. Article 100 defines a continuous load as one whose maximum current is expected to continue for 3 hours or more. The 125% factor exists because standard overcurrent devices are listed for continuous operation at only 80% of their rating, so the two numbers are the same rule seen from opposite ends. The 210.20(A) and 215.3 exceptions allow a factor of 100% where the assembly is listed for operation at 100% of its rating. Standard ratings come from 240.6(A). These rules are unchanged across the 2017, 2020, and 2023 editions.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

The 80% rule at a glance: continuous load per breaker

Breaker / fuse Max continuous load (80%) Max noncontinuous load (100%)
15 A12 A15 A
20 A16 A20 A
30 A24 A30 A
50 A40 A50 A
100 A80 A100 A
200 A160 A200 A

Max continuous load is the rating divided by 1.25, which is the same as 80% of the rating. A load that runs less than 3 hours is noncontinuous and may use the full rating. Mixed loads fall between the two columns; enter them above for the exact headroom.

125% and 80% are one rule seen from two ends

NEC 210.20(A) says the overcurrent device is rated at not less than the noncontinuous load plus 125% of the continuous load. Turn that around for an all-continuous load and it says the load may be at most the rating divided by 1.25, which is 80% of the rating. Standard breakers and fuses are tested and listed to carry only 80% of their rating continuously, which is why the code builds the 25% margin into the sizing. Sizing a circuit and checking a circuit are therefore the same equation; this tool just solves it for whichever quantity you are missing.

Worked example: a 100 A continuous load needs 100 x 1.25 = 125 A of overcurrent protection and conductor ampacity, so a 125 A device. Run it the other way and a 125 A device carries 125 / 1.25 = 100 A of continuous load. A 30 A continuous load needs 37.5 A, which is not a standard size, so it rounds up to a 40 A device under 240.6(A).

Mixed continuous and noncontinuous loads

Most real circuits carry both kinds of load. The rule adds 125% of the continuous part to 100% of the noncontinuous part. A circuit with 24 A of continuous load and 10 A of noncontinuous load needs 10 + (24 x 1.25) = 40 A of protection. Going the other way, a 50 A feeder that already carries 20 A continuous and 10 A noncontinuous has used 10 + (20 x 1.25) = 35 A of its 50 A, leaving room for 12 A more continuous load or 15 A more noncontinuous load before it needs to grow.

This tool stops at the ampere rule, on purpose

The 210.20(A) continuous-load rule is one step inside every conductor-sizing job. This calculator isolates that step so you can see it clearly and run it backward. It reports the minimum device rating and the conductor ampacity, but it deliberately does not pick a wire gauge: choosing the AWG needs Table 310.16, the 110.14(C) termination limit, ambient and conductor-count derating, and the 240.4(B) and 240.4(D) conductor-protection rules. Carry the conductor ampacity this tool returns into the Wire Size or Wire Ampacity calculator to finish that step. Motor loads are also out of scope: a motor branch circuit is sized from the Table 430.248 or 430.250 full-load current and Article 430 percentages, not the 125% continuous rule.

Frequently asked questions

Why 125% and not exactly 100%?

A standard molded-case breaker is calibrated and listed to carry 80% of its rating continuously without its terminals overheating. Adding 25% to a continuous load (1 / 0.80 = 1.25) restores that margin, so the device runs within its listing for the full 3 hours or more that a continuous load stays on.

Is a receptacle circuit a continuous load?

Usually not. General-purpose receptacles serving cord-and-plug tools and appliances that come and go are noncontinuous. But a receptacle dedicated to a load that runs 3 hours or more, such as an EV charger or a sign, is continuous. Classify by how the load actually runs, not by the outlet type.

Does this apply to feeders and services?

Yes. NEC 215.3 applies the identical noncontinuous-plus-125%-continuous rule to feeder overcurrent devices, and 215.2(A)(1) to feeder conductors. Service and feeder load calculations under Article 220 are a separate step that produces the load figure you then feed into this rule.

Does the 80% number change the wire size?

The 125% figure sets the minimum ampacity the conductor must have before derating, which can push the wire larger. It is not the same as the temperature and conductor-count adjustments, which come after. This tool gives you the required ampacity; the Wire Size calculator turns it into an AWG.

Related calculators

Seasonal safety guide

Loading a holiday display onto a household circuit rather than sizing a branch circuit? This homeowner guide uses the same 80 percent rule.

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.

For deeper NEC training on continuous-load and branch-circuit sizing, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.