Service Disconnect Grouping & Load Marking Calculator
Check the NEC 230.72 and 230.70 installation rules for the service disconnecting means: whether the two to six disconnects must be grouped, the two required markings (service disconnect per 230.70(B) and load served per 230.72(A)), the 230.70(C) suitability rule, and the 230.72(B) requirement that a fire pump, emergency, or standby disconnect be kept remote. Set the count and the installation details for a compliance verdict.
How to use this calculator
- Set the number of service disconnecting means (one to six per 230.71(B)).
- Say whether an additional fire pump, emergency, or standby service disconnect is present.
- Optionally confirm grouping (if two to six), the service-disconnect and load-served markings, and suitability for the conditions.
- If an additional-system disconnect is present, say whether it is located remote from the normal disconnects.
- Read the per-requirement checklist and the overall verdict: meets code, does not meet code, or needs review when a condition is still unconfirmed.
NEC reference
This calculator implements NEC 2020 Article 230, Part VI. Section 230.72(A) requires the two to six service disconnecting means permitted by 230.71 to be grouped and each marked to indicate the load served, with an exception for a single water-pump/fire-protection disconnect. Section 230.72(B) requires the additional service disconnecting means for fire pumps, emergency systems, legally required standby, and optional standby services to be located remote from the normal service disconnects. Section 230.70(B) requires each service disconnecting means to be permanently marked to identify it as a service disconnect, and 230.70(C) requires each to be suitable for the prevailing conditions. NEC 2020 is the site default.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
The five requirements, with the right citations
Article 230 Part VI spreads the service-disconnect installation rules across two sections. Getting the citation right matters on an inspection: the two markings live in different sections, and the load-served marking is commonly miscited to 230.70(B) when it is actually a 230.72(A) grouping requirement.
| Requirement | Applies when | Source |
|---|---|---|
| Grouped | Two to six disconnects | 230.72(A) |
| Marked with the load served | Two to six disconnects | 230.72(A) |
| Marked as a service disconnect | Every service disconnect | 230.70(B) |
| Suitable for the prevailing conditions | Every service disconnect | 230.70(C) |
| Located remote from normal disconnects | Fire pump / emergency / standby disconnect | 230.72(B) |
Why the load-served marking is 230.72(A), not 230.70(B)
Two markings are easy to confuse. 230.70(B) is the identification marking: every service disconnecting means is permanently marked to identify it as a service disconnect, so anyone at the panel knows the device ahead of them is the service. 230.72(A) is a grouping rule, and it adds that where two to six disconnects are grouped, each is marked to indicate the load served (for example which unit, panel, or system it feeds). A compliant installation carries both: the service-disconnect identification from 230.70(B) and the load-served label from 230.72(A). A single service disconnect needs the 230.70(B) marking; the 230.72(A) load-served marking is about telling grouped disconnects apart.
Grouping and the water-pump exception
Grouping means the two to six disconnects are located together so the service can be shut off from one place. What qualifies as grouped (a single assembly, adjacent enclosures, or a common area) is an AHJ judgment, so place them deliberately rather than scattered around a building. 230.72(A) carries one exception: a single disconnect that supplies only a water pump also intended to provide fire protection may be located remote from the others, provided a permanent plaque or directory at the grouped disconnects points to it. This tool surfaces the exception but does not treat it as satisfying the grouping rule, because it cannot verify that the remote disconnect serves only that water pump or that the plaque is installed; a grouping failure stays noncompliant until you confirm those facts on site.
Keeping fire pump and standby disconnects remote
230.72(B) covers the extra service disconnecting means allowed by 230.2 for fire pumps, emergency systems, legally required standby systems, and optional standby systems. Those disconnects must be remote from the one to six normal service disconnects. The reason is simple: if the fire pump disconnect sat in the same group as the normal service and a responder or a fault took the whole group down, the building would lose its fire pump at the worst possible moment. Keeping it remote means a shutdown of normal service does not also drop the life-safety or standby load.
Worked examples
A small commercial building has three service disconnects, each in its own enclosure, mounted side by side on the same wall. They are grouped (230.72(A)), each is labeled as a service disconnect (230.70(B)) and with the panel it feeds (230.72(A)), and all three are in NEMA 3R enclosures outdoors (230.70(C)). With no fire pump or standby service, the installation meets 230.72 / 230.70.
The same building adds a fire pump fed from its own service disconnect. If that disconnect is bolted into the same group as the three normal disconnects, 230.72(B) is violated: it must be relocated remote from the normal service group. Move it to a separate location and the installation complies again.
Common mistakes
- Scattering the disconnects. Two to six service disconnects must be grouped, not spread around the building.
- Skipping the load-served label. Grouped disconnects each need a marking that says what they feed (230.72(A)), on top of the service-disconnect identification (230.70(B)).
- Citing the load-served marking to the wrong section. It is a 230.72(A) grouping requirement, not 230.70(B).
- Grouping the fire pump disconnect with the normal service. 230.72(B) requires it remote so a normal-service shutdown does not drop the fire pump.
- Using an indoor-rated enclosure outdoors. 230.70(C) requires each disconnect to be suitable for the prevailing conditions.
Frequently asked questions
Do service disconnects have to be grouped?
Yes, where two to six are provided (230.72(A)). A single disconnect has nothing to group. One of the two to six serving only a fire-protection water pump may be remote, with a plaque at the group pointing to it.
What marking does a service disconnect need?
Two markings: identify it as a service disconnect (230.70(B)), and, for grouped disconnects, indicate the load served (230.72(A)). Both must be permanent and legible per 110.21(B).
Where does a fire pump or standby disconnect go?
Remote from the normal service disconnects (230.72(B)), so a shutdown of normal service does not simultaneously interrupt the fire pump, emergency, or standby supply.
How many service disconnects does the NEC allow?
One to six per 230.71(B), each in its own enclosure in the 2020 NEC. The count and the minimum rating (230.79/230.80) are handled by the Service Disconnect Number and Rating Calculator; this tool checks grouping, marking, suitability, and the remote rule.
Is the load-served marking in 230.70(B) or 230.72(A)?
230.72(A). 230.70(B) only requires the service-disconnect identification. A compliant installation carries both markings.
Related calculators
- Service Disconnect Number & Rating Calculator: how many service disconnects the NEC allows and their minimum rating per 230.71, 230.79, and 230.80.
- Emergency Disconnect Requirement Calculator: the NEC 230.85 outdoor emergency disconnect and marking for one- and two-family dwellings.
- Service Size Calculator: size service-entrance conductors and the grounding electrode conductor from a known load.
- Working Space Clearance Calculator: required depth, width, and headroom in front of the service equipment per NEC 110.26(A).
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.
For deeper NEC training on service equipment and disconnects, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.
Get new tools and reference cards by email
Occasional emails when a new calculator, guide, or printable card ships. No spam, unsubscribe anytime.