Surge-Protective Device (SPD) Requirement Calculator
Pick the service and the work scenario to see whether NEC 2020 230.67 requires a surge-protective device, which Type satisfies it, where it has to mount, and whether replacing existing service equipment triggers the rule. The 230.67 service-SPD mandate was new in the 2020 National Electrical Code (NEC), and a panel swap is one of the places it catches people.
How to use this calculator
- Choose what the service supplies: a dwelling unit (the 2020 mandate) or only non-dwelling occupancies.
- Pick the work scenario: a new service, a replacement of existing service equipment (230.67(D)), or an existing service you are not touching.
- Optionally select the SPD Type you plan to use so the tool can confirm it against 230.67(C) and reject a Type 3 strip.
- Optionally pick the installed location to see the 230.67(B) rule and the next-level-distribution exception, then read the notes for the full citation chain.
NEC reference
The requirement is NEC 2020 230.67. Subsection (A) requires a surge-protective device on all services supplying dwelling units; subsection (B) sets the location (integral to or immediately adjacent to the service equipment, with an exception for an SPD at each next-level distribution equipment downstream); subsection (C) requires a Type 1 or Type 2 SPD; and subsection (D) makes the whole section apply where service equipment is replaced. 230.67 was added in the 2020 edition, so a jurisdiction still on the 2017 NEC has no service-SPD mandate, and the 2023 edition expands the covered occupancies and adds a minimum-rating subsection, both outside this tool's 2020 scope.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
What NEC 2020 230.67 says
Section 230.67 is short and has four parts. It applies to the service, not to individual branch circuits, which is why it belongs with the service and disconnect rules rather than with the GFCI and AFCI device sections.
| Subsection | What it requires |
|---|---|
| 230.67(A) | An SPD on all services supplying dwelling units. |
| 230.67(B) | Integral to or immediately adjacent to the service equipment; or, by exception, at each next-level distribution equipment downstream. |
| 230.67(C) | The SPD shall be a Type 1 or Type 2 device. |
| 230.67(D) | Where service equipment is replaced, all of 230.67 applies. |
Table values and section numbers are referenced for identification only, not reproduced from the NEC verbatim.
Type 1 versus Type 2: which one and where
230.67(C) accepts either a Type 1 or a Type 2 SPD, and the difference is where it connects. A Type 1 SPD is permanently connected between the utility transformer secondary and the service disconnect overcurrent device, so it can land on the line side or the load side of the main and needs no separate overcurrent protection. A Type 2 SPD is permanently connected on the load side of the service disconnect overcurrent device, which includes a position at a branch panelboard. A Type 3 SPD is a plug-in, point-of-use device, usually cord-connected at least 30 ft of conductor from the service, and it does not satisfy the 230.67 service requirement.
The replacement trigger catches remodels
230.67(D) is the part electricians miss. A dwelling built under the 2014 or 2017 NEC has no SPD, and the code is not retroactive, so it stays compliant as installed. But the moment the service equipment is replaced, such as a panel change or a service upgrade, 230.67(D) makes the entire section apply, and the new installation needs a Type 1 or Type 2 SPD. Treat a service-equipment swap on a 2020-code job as an SPD job.
Frequently asked questions
Is a plug-in surge strip enough for code?
No. A plug-in surge strip is a Type 3 point-of-use device, and 230.67(C) requires a Type 1 or Type 2 SPD at or near the service. A Type 3 device can be used as supplementary protection for sensitive electronics, but it does not satisfy the service requirement.
Do commercial or industrial services need an SPD?
Not under the 2020 NEC. 230.67(A) scopes the service-SPD mandate to services supplying dwelling units. The 2023 edition expands it to dormitory units, guest rooms and guest suites, and certain nursing-home and limited-care sleeping areas, so on a 2023-code job re-check the scope for the occupancy you are serving.
Does a multifamily building need SPDs?
A service supplying dwelling units falls under 230.67(A), so a service to an apartment or condo building that feeds dwelling units is covered. Where the SPD sits follows 230.67(B): at the service, or an SPD at each next-level distribution panel under the exception.
Does this size the SPD's rating?
No. This tool answers the 230.67 requirement, Type, and location. Match the SPD's voltage rating to the nominal system voltage and confirm its short-circuit current rating against the available fault current per the manufacturer's instructions and 110.3(B); fault-current analysis is outside this tool.
Related calculators
- GFCI Breaker Sizing Calculator: the NEC 210.8 ground-fault requirement by location and GFCI breaker sizing.
- AFCI Requirement & Breaker Sizing Calculator: the NEC 210.12 arc-fault requirement for dwelling rooms.
- Service Disconnect Number & Rating Calculator: the 230.71 one-to-six service disconnect rule and rating.
- Service Size Calculator: the dwelling service and feeder load calculation.
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.
For deeper NEC training on surge protection and service equipment, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.
Get new tools and reference cards by email
Occasional emails when a new calculator, guide, or printable card ships. No spam, unsubscribe anytime.