ElectricalToolbox

Room Air Conditioner Branch Circuit Calculator

Size the branch circuit for a cord-and-plug room air conditioner under NEC 2020 440.62. Enter the unit's marked rating and whether the circuit is dedicated or shared, and the tool returns the minimum standard branch-circuit rating: the 80% rule (440.62(B)) when the room air conditioner is the only load, or the 50% rule (440.62(C)) when lighting or receptacles share the circuit.

Room air conditioner

Enter the total rated-load current marked on the nameplate (NEC 440.62(A)(3)), not the compressor and fan currents separately. NEC 440.62 covers cord-and-plug units rated 40 A, 250 V, single phase or less.

What else is on the circuit?

A dedicated circuit lets the unit use up to 80% of the circuit rating. If the circuit also feeds lighting outlets, general-use receptacles, or other appliances, the limit drops to 50%.

How to use this calculator

  1. Enter the total rated-load current marked on the room air conditioner nameplate (NEC 440.62(A)(3)).
  2. Pick the nominal voltage. NEC 440.62 covers single-phase units rated 250 V or less.
  3. Choose whether the circuit is dedicated (room AC only, 80%) or shared with lighting/receptacles (50%).
  4. Read the minimum standard branch-circuit rating and the max-room-AC-per-circuit reference table.
  5. Size the conductor and confirm the receptacle rating with the Wire Size and Breaker Size calculators (NEC 440.62(A)(4)).

NEC reference

This tool applies NEC 2020 440.62 (Branch Circuits), in Article 440, Part VII, Room Air Conditioners. Section 440.62(A) sets when a room air conditioner is treated as a single motor unit for branch-circuit sizing: it must be cord- and attachment-plug-connected, rated 40 A, 250 V, single phase or less, with the total rated-load current marked on the nameplate, and the branch-circuit overcurrent device must not exceed the conductor ampacity or the receptacle rating. Section 440.62(B) limits the marked rating to 80% of the branch-circuit rating where no other loads are on the circuit; 440.62(C) limits it to 50% where lighting outlets, other appliances, or general-use receptacles are also supplied. Standard branch-circuit ratings are from NEC 210.3. The National Electrical Code (NEC) edition referenced is 2020, the site default.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

The 80% and 50% rules (440.62(B) and 440.62(C))

A cord-and-plug room air conditioner is a continuous motor load on a branch circuit that often serves other things, so NEC 440.62 caps how much of the circuit the unit may take. On a dedicated circuit - the room air conditioner is the only load - the marked rating may not exceed 80% of the branch-circuit rating (440.62(B)). Where the same circuit also feeds lighting outlets, general-use receptacles, or other appliances, the limit drops to 50% (440.62(C)), because the other loads share the circuit's capacity.

Reading the rule backward gives the minimum circuit: the branch-circuit rating must be at least the marked rating divided by 0.80 (dedicated) or 0.50 (shared), rounded up to the next standard branch-circuit rating (15, 20, 30, 40, or 50 A per NEC 210.3). A 12 A unit needs a 15 A dedicated circuit, but a 30 A circuit if it must share with the room's lighting.

What counts as a room air conditioner (440.62(A))

Section 440.62 applies only to a unit that meets all of 440.62(A): it is cord- and attachment-plug-connected; its rating is 40 A, 250 V, single phase or less; the total rated-load current is marked on the nameplate rather than the separate compressor and fan motor currents; and the branch-circuit short-circuit and ground-fault protective device does not exceed the branch-circuit conductor ampacity or the receptacle rating, whichever is less. A permanently connected (hard-wired) unit, anything over 40 A or 250 V, or three-phase equipment falls outside 440.62 and is sized by the general Article 440 rules for hermetic-compressor equipment - use the MCA and MOCP calculator.

Worked examples

  • 12 A unit, dedicated circuit. 12 A / 0.80 = 15 A, and 0.80 x 15 = 12 A, so a 15 A dedicated circuit is the minimum. This is the familiar "12 amp window unit on a 15 amp circuit."
  • 12 A unit sharing with room lighting. The 50% rule applies: 12 A / 0.50 = 24 A. A 20 A circuit allows only 0.50 x 20 = 10 A, so the minimum is a 30 A circuit (0.50 x 30 = 15 A). Sharing the circuit forces a bigger breaker for the same unit.
  • 16 A unit, dedicated circuit. 16 A / 0.80 = 20 A, and 0.80 x 20 = 16 A exactly, so a 20 A dedicated circuit is the minimum.
  • 40 A unit sharing a circuit. 40 A / 0.50 = 80 A. No standard branch circuit up to 50 A meets the 50% limit (0.50 x 50 = 25 A), so a 40 A room air conditioner must be on its own dedicated circuit, where it needs a 50 A circuit.

Frequently asked questions

What size breaker for a window air conditioner?

NEC 440.62 sizes the circuit from the unit's marked rating. On a dedicated circuit the marked rating may not exceed 80% of the circuit rating, so a 12 A unit needs at least a 15 A circuit. On a shared circuit the limit is 50%. Enter the marked rating above for the minimum standard rating, then size the conductor with the Wire Size calculator.

Can a room air conditioner share a circuit with outlets?

Yes, but under the 50% rule (440.62(C)) the unit's marked rating may not exceed half the branch-circuit rating, which usually forces a larger circuit than a dedicated one would. A dedicated circuit for the room air conditioner is often the simpler and cheaper choice.

Do I still have to size the wire?

Yes. This tool applies the 440.62 percentage rule to find the minimum branch-circuit rating. NEC 440.62(A)(4) also requires the overcurrent device not to exceed the conductor ampacity or the receptacle rating - size the conductor with the Wire Size or Wire Ampacity calculator and confirm the receptacle.

Which NEC edition is this?

NEC 2020. The 440.62 room-air-conditioner rule and the 80%/50% branch-circuit limits are unchanged across the 2017, 2020, and 2023 editions. Always confirm the edition your jurisdiction has adopted.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.

For deeper NEC training on room air conditioners and branch circuits, Mike Holt's NEC courses are the industry standard.