ElectricalToolbox

Solar 120% Rule Calculator

Check a load-side PV or battery interconnection against NEC 2020 705.12(B)(3). Enter the busbar rating, the main overcurrent device that protects it, and the inverter output current; the tool applies the 125 percent source term, tests both the sum method and the 120 percent method, and returns the maximum source output current and the largest standard backfed overcurrent device the busbar allows.

Panel and source

The busbar (bus) ampere rating and the rating of the overcurrent device protecting it (the main breaker, or the upstream feeder OCPD for a main-lug panel). The source output current is the combined continuous output of the interconnected inverter(s); the tool applies 125% to it per 705.12(B)(3).

How to use this calculator

  1. Enter the busbar (bus) ampere rating from the panelboard label, for example 200 A.
  2. Enter the rating of the overcurrent device protecting the busbar, usually the main breaker; for a main-lug panel use the upstream feeder device.
  3. Enter the combined continuous output current of the interconnected inverter(s); the tool multiplies it by 125 percent per 705.12(B)(3).
  4. Read the pass or fail for the sum method (1) and the 120 percent method (2), with the busbar loading shown for each.
  5. Use the maximum source output current and largest standard backfed overcurrent device to size or confirm the interconnection.

NEC reference

This calculator follows NEC 2020 Section 705.12(B)(3), which governs how a power production source connects to a busbar. Option 705.12(B)(3)(1) requires the sum of 125 percent of the power source output circuit current and the rating of the overcurrent device protecting the busbar to be within the busbar ampacity. Option 705.12(B)(3)(2), the 120 percent rule, permits that sum to reach 120 percent of the busbar ampacity when the two sources are at opposite ends of a busbar that contains the loads between them and the backfed device position is marked so it is not relocated. Standard overcurrent device ratings come from 240.6(A), and the backfed device is a continuous load rated at not less than 125 percent of the source output current per 705.60. The method is materially unchanged in the 2023 edition.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

The 120% rule, step by step

A panelboard busbar is normally protected by a single main overcurrent device sized to the busbar rating. Backfeeding a solar or storage inverter into the same busbar adds a second supply, so the bus can now carry current from both ends. NEC 705.12(B)(3) keeps the busbar from being overloaded. The busbar loading term is 125 percent of the source output circuit current, because a PV or battery output circuit is a continuous load. Add the main overcurrent device rating and compare the total against the busbar.

Option (1) is the plain sum: 125 percent of the source current plus the main must fit within the busbar rating, and the backfed device can go anywhere. Option (2), the 120 percent rule, recognizes that when the utility feeds one end of the bus and the inverter feeds the opposite end, with the loads tapped in between, no single section of the bus ever carries the full combined current. That geometry lets the sum reach 120 percent of the busbar rating, provided the backfed device sits at the far end and the panel is marked so it stays there.

Worked example: 200 A busbar, 200 A main

  1. The busbar is rated 200 A and the main breaker protecting it is 200 A.
  2. Option (1): the main alone already equals the busbar, so there is no room for any source at 100 percent.
  3. Option (2): 120 percent of 200 A is 240 A. Subtract the 200 A main and 40 A of busbar headroom remains.
  4. The source term is 125 percent of the inverter output current, so the largest inverter output is 40 divided by 1.25, which is 32 A continuous.
  5. The largest standard backfed overcurrent device at or below the 40 A headroom is a 40 A breaker, sized for that 32 A continuous output.
  6. The backfed breaker must be at the opposite end of the busbar from the main, and the panel must be marked so it is not relocated.

Source current versus breaker rating

The 2020 NEC busbar term is 125 percent of the power source output circuit current, a current, not the backfed breaker rating. Earlier editions and many quick rules of thumb used the breaker rating, which is slightly larger because it is rounded up to a standard 240.6(A) size. This tool holds to the 2020 language: the pass and fail results and the maximum source output current come from 125 percent of the source current. It also reports the largest standard backfed overcurrent device on the conservative breaker basis, since the installed device is itself at least 125 percent of the source current, so a breaker within the busbar headroom always clears the code check. Both figures are correct; the breaker number is the never-over-permit answer.

Other 705.12(B)(3) options

Beyond the sum method and the 120 percent rule, 705.12(B)(3)(3) permits the sum of the ampere ratings of all overcurrent devices on the panel, both load and supply, excluding the busbar device, to equal the busbar rating; it is independent of the main rating but needs the full breaker schedule, so this tool documents it rather than computing it. Option 705.12(B)(3)(4) applies the same 120 percent arithmetic to a center-fed panelboard in a dwelling with the connection at one end only, and 705.12(B)(3)(5) permits multiple-ampacity busbars designed under engineering supervision with fault-current and busbar-load calculations. When no busbar method works, a supply-side connection under 705.11 has no 120 percent limit and is often the answer for a large system on a fully loaded service.

Frequently asked questions

What is the 120% rule for solar?

NEC 705.12(B)(3)(2): with the utility and the inverter at opposite ends of a busbar and loads between them, 125 percent of the source output current plus the main overcurrent device rating may reach 120 percent of the busbar rating instead of 100 percent. A 200 A busbar with a 200 A main leaves room for a 40 A backfed breaker.

How do I calculate the maximum backfeed breaker?

Take 1.2 times the busbar rating, subtract the main rating, and pick the largest standard 240.6(A) device at or below that headroom. For 200 A and 200 A that is 240 minus 200, so a 40 A backfed breaker.

Where must the backfeed breaker go?

For the 120 percent method it must be at the opposite end of the busbar from the main, with the panel marked so it is not relocated. If it can sit anywhere, the full sum must fit within 100 percent of the busbar under method (1).

Inverter current or breaker rating?

The 2020 code uses 125 percent of the source output circuit current, not the breaker rating. This tool computes pass and fail from the code exact current and reports the standard breaker separately.

What if my system fails?

Reduce the main rating, reduce the inverter output, use a higher busbar rating, use the sum-of-all-devices method, or move to a supply-side connection under 705.11, which has no 120 percent limit.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

For deeper NEC training on NEC 705.12 solar and storage interconnection and the 120% rule, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.