AWG Calculator

Convert AWG and kcmil conductor sizes to mm² and back, using the published areas from NEC Chapter 9, Table 8. 18 AWG through 2000 kcmil. Includes the IEC 60228 metric cross-reference with the equal-or-larger substitution called out explicitly.

Conversion direction
AWG/kcmil size

How to use this calculator

  1. Pick the conversion direction: AWG/kcmil → mm², or mm² → AWG/kcmil.
  2. Select the conductor size (or enter a metric cross-section. The dropdown pre-fills IEC 60228 standard sizes).
  3. Read the published Table 8 areas in circular mils, kcmil, and mm².
  4. For metric-to-AWG, use the "smallest AWG ≥ input area" result for substitution. It is the size that never reduces the conductor cross-section. The nearest-by-area size is shown for reference and may be smaller than your input.

NEC reference

Areas are the published values from NEC 2020 Chapter 9, Table 8 (Conductor Properties). Both the circular-mil and mm² columns. These values are unchanged across the 2017, 2020, and 2023 editions. IEC 60228 nominal cross-sections are an international cable standard, not NEC data; the cross-reference is informational. This tool converts area only. It makes no ampacity determination (see the FAQ below).

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

AWG to mm² conversion chart (NEC Chapter 9, Table 8)

Full published conversion table, 18 AWG through 2000 kcmil. The mm² column is the NEC-published figure, not a recomputed approximation.

Size Circular mils mm²
18 AWG 1,620 0.823
16 AWG 2,580 1.31
14 AWG 4,110 2.08
12 AWG 6,530 3.31
10 AWG 10,380 5.261
8 AWG 16,510 8.367
6 AWG 26,240 13.3
4 AWG 41,740 21.15
3 AWG 52,620 26.67
2 AWG 66,360 33.62
1 AWG 83,690 42.41
1/0 AWG 105,600 53.49
2/0 AWG 133,100 67.43
3/0 AWG 167,800 85.01
4/0 AWG 211,600 107.2
250 kcmil 250,000 127
300 kcmil 300,000 152
350 kcmil 350,000 177
400 kcmil 400,000 203
500 kcmil 500,000 253
600 kcmil 600,000 304
700 kcmil 700,000 355
750 kcmil 750,000 380
800 kcmil 800,000 405
900 kcmil 900,000 456
1000 kcmil 1,000,000 507
1250 kcmil 1,250,000 633
1500 kcmil 1,500,000 760
1750 kcmil 1,750,000 887
2000 kcmil 2,000,000 1013

Source: NEC 2020 Chapter 9, Table 8 (Conductor Properties). Identity: 1 cmil = 5.067 × 10⁻⁴ mm².

AWG vs IEC 60228 quick reference

Common substitution pairs, safe direction only (metric size shown is equal to or larger than the AWG conductor it replaces, and vice versa). Area equivalence does not establish ampacity equivalence. The governing code's ampacity table still applies.

AWG (mm²) IEC size that is equal or larger
14 AWG (2.08)2.5 mm²
12 AWG (3.31)4 mm²
10 AWG (5.261)6 mm²
8 AWG (8.367)10 mm²
6 AWG (13.30)16 mm²
4 AWG (21.15)25 mm²
2 AWG (33.62)35 mm²
1/0 AWG (53.49)70 mm²
4/0 AWG (107.2)120 mm²

Frequently asked questions

What is 12 AWG in mm²?

12 AWG is 3.31 mm² (6,530 circular mils) per NEC Chapter 9, Table 8. The nearest IEC 60228 size is 4 mm². About 21% larger. For substitution, 4 mm² replaces 12 AWG in the safe direction; 2.5 mm² is smaller than 12 AWG and is not an equivalent.

How do you convert AWG to mm²?

Read the area directly from NEC Chapter 9, Table 8, which publishes both columns. The identity behind the table is 1 circular mil = 5.067 × 10⁻⁴ mm² (the area of a 0.001-inch-diameter circle). For kcmil sizes: mm² = kcmil × 0.5067. Worked example: 4/0 AWG = 211,600 cmil; 211,600 × 0.0005067 ≈ 107.2 mm². Matching the published value.

Is 2.5 mm² equivalent to 14 AWG?

No. 2.5 mm² (2.5) is larger than 14 AWG (2.08 mm²) and smaller than 12 AWG (3.31 mm²). Replacing 2.5 mm² cable with 14 AWG reduces the copper cross-section by roughly 17%. The wrong direction. The equal-or-larger substitution for 2.5 mm² is 12 AWG.

Why do published mm² values differ slightly from cmil × 0.0005067?

For small AWG sizes the NEC converts from the exact AWG-defined conductor diameter rather than the rounded circular-mil figure, so the published mm² can differ in the third digit (18 AWG: 1,620 cmil × 0.0005067 = 0.821 mm², published 0.823 mm²). This tool reports the published Table 8 values.

Does area equivalence mean ampacity equivalence?

No. NEC ampacity comes from Table 310.16 (or the table for the applicable wiring method) under NEC assumptions; IEC 60228 conductors are rated under IEC 60364-5-52 with different ambient bases and installation methods. Use this tool for the area conversion, then verify ampacity under the code governing the installation. The Wire Ampacity Calculator handles the NEC side.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

For deeper NEC training on wire sizing and conversion, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.