ElectricalToolbox

Motor Full-Load Current Calculator

Look up a motor's full-load current (FLC) from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase) by horsepower and voltage, the table value used for branch-circuit and feeder sizing per NEC 430.6(A)(1). The tool also shows the 430.22 branch-circuit conductor minimum ampacity (125 percent of FLC).

Motor

The full-load current is the NEC Table 430.248/430.250 value for the horsepower and voltage (NEC 430.6(A)(1)), used for branch-circuit and feeder sizing, not the motor nameplate current.

How to use this calculator

  1. Choose the motor phase: single-phase (Table 430.248) or three-phase (Table 430.250).
  2. Select the system voltage from the listed table columns for that phase.
  3. Select the motor horsepower.
  4. Read the table full-load current and the 430.22 branch-circuit conductor minimum ampacity (125 percent of FLC).

NEC reference

This lookup reads NEC 2020 Table 430.248 (full-load current of single-phase AC motors) and Table 430.250 (full-load current of three-phase AC induction motors). The table value, not the motor nameplate current, is used for conductor sizing (430.22) and branch-circuit protection (430.52) per NEC 430.6(A)(1). The 125 percent branch-circuit conductor rule is NEC 430.22. These values are unchanged across the 2017, 2020, and 2023 editions.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

Table FLC vs. nameplate current

A motor's nameplate lists a full-load amps (FLA) value measured for that specific machine. The NEC deliberately does not use it for general circuit sizing. NEC 430.6(A)(1) directs that conductor ampacity, branch-circuit short-circuit and ground-fault protection, and the disconnecting means all be sized from the tabulated full-load current in Tables 430.247 through 430.250, selected by horsepower and voltage. The tables give a single, conservative, code-consistent value so two electricians sizing the same 10 hp, 460 V circuit always land on the same 14 A basis.

The nameplate current has exactly one job in the NEC scheme: the running overload protection (NEC 430.6(A)(2) and 430.32), which protects the motor itself and is sized on the actual nameplate FLA. That is a separate calculation handled by the Motor Overload Protection Calculator.

Sizing the conductor: NEC 430.22

Once you have the table FLC, the branch-circuit conductors of a single continuous-duty motor must carry at least 125 percent of it:

minimum conductor ampacity = table FLC x 125%

This is a required ampacity in amperes, not a wire gauge. You still select the actual conductor from Table 310.16 at the equipment's termination temperature (typically the 75 degree C column) and apply any ambient-temperature or more-than-three-conductor derating. The Wire Gauge and Wire Ampacity calculators do that step.

Worked examples

Three-phase, 460 V. A 10 hp, 460 V three-phase motor: Table 430.250 lists 14 A.

FLC = 14 A; conductor min = 14 A x 125% = 17.5 A

Single-phase, 115 V. A 1 hp, 115 V single-phase motor: Table 430.248 lists 16 A.

FLC = 16 A; conductor min = 16 A x 125% = 20 A

Voltage matters. The same 10 hp three-phase motor is 28 A at 230 V but 14 A at 460 V, because current scales inversely with voltage for a given horsepower, which is why larger motor feeders are usually run at 460 V.

How this differs from the other motor tools

This page is the raw table lookup: the full-load current and the one conductor figure that follows straight from it. The tools that compute a device rating take it from here:

Frequently asked questions

Where does motor full-load current come from?

From NEC Table 430.248 (single-phase) or Table 430.250 (three-phase) by horsepower and voltage. Per NEC 430.6(A)(1), this table value, not the motor nameplate current, sizes the branch circuit and feeder. A 10 hp, 460 V three-phase motor is 14 A.

Nameplate current or table FLC?

Table FLC for conductor ampacity (430.22), branch-circuit protection (430.52), and the disconnect (430.110). The nameplate FLA is used only for the running overload (430.32).

How do I size the conductor from FLC?

Take 125 percent of the table FLC (NEC 430.22) to get the required ampacity, then pick the conductor from Table 310.16 at the termination temperature with any derating. A 10 hp, 460 V motor needs 14 x 1.25 = 17.5 A of ampacity.

Which motor types are covered?

Single-phase AC motors (Table 430.248) and three-phase AC induction motors, squirrel-cage and wound-rotor (Table 430.250). Synchronous and DC motors have their own tables and are outside this lookup.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

For deeper NEC training on motor circuits and controls, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.

This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.