Dwelling Lighting Outlet Requirements Calculator

Check where a lighting outlet is required in a dwelling unit and what control it needs under National Electrical Code (NEC) 210.70(A). Pick the room or location for the requirement, the permitted substitutions (a switched receptacle or an occupancy sensor), and the six-riser stairway switching rule.

The location

How to use this calculator

  1. Select the dwelling location: a habitable room, kitchen, bathroom, hallway, interior stairway, attached or detached garage, outdoor entrance, or a storage/equipment space.
  2. Read whether a lighting outlet is required and the control it needs (wall switch, or a wall switch at each level for a stairway).
  3. For an interior stairway, enter the number of risers between floor levels: six or more triggers the switch-at-each-level rule.
  4. For a detached garage or a storage/equipment space, answer the electric-power or use question that decides whether the requirement applies.
  5. Read the notes for the permitted substitutions: a switched receptacle in lieu (habitable rooms other than kitchens and bathrooms), occupancy sensors, and remote or automatic control in hallways, stairways, and at outdoor entrances.

NEC reference

This calculator implements NEC 2020 210.70(A), the required lighting outlets in dwelling units: 210.70(A)(1) covers habitable rooms and bathrooms with its two exceptions (a switched receptacle in lieu, and occupancy-sensor control), 210.70(A)(2) covers hallways, stairways, garages, and outdoor entrances (including the six-riser interior-stairway switching rule and the remote/central/automatic control exception), and 210.70(A)(3) covers storage or equipment spaces (attics, under-floor spaces, utility rooms, and basements) used for storage or containing equipment requiring servicing.

Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.

Where a lighting outlet is required, at a glance

210.70(A) sets the required lighting outlets for a dwelling unit by location. Most are a flat requirement; a stairway adds a switching rule at six risers, and a detached garage and a storage/equipment space carry a condition that decides whether the requirement applies.

Location Requirement NEC
Habitable room (bedroom, living room, den) Wall switch-controlled lighting outlet; switched receptacle in lieu permitted 210.70(A)(1)
Kitchen Wall switch-controlled lighting outlet (no switched-receptacle substitute) 210.70(A)(1)
Bathroom Wall switch-controlled lighting outlet (no switched-receptacle substitute) 210.70(A)(1)
Hallway Wall switch-controlled lighting outlet 210.70(A)(2)(a)
Interior stairway Wall switch-controlled lighting outlet; switch at each level at six or more risers 210.70(A)(2)(a), (c)
Attached garage Wall switch-controlled lighting outlet 210.70(A)(2)(a)
Detached garage Required only where it has electric power 210.70(A)(2)(a)
Outdoor entrance / exit, grade-level access Wall switch-controlled lighting outlet on the exterior side 210.70(A)(2)(b)
Attic / under-floor / utility room / basement Required only where used for storage or containing serviceable equipment 210.70(A)(3)

The kitchen and bathroom exclusion

210.70(A)(1) requires a wall switch-controlled lighting outlet in every habitable room and bathroom. Exception 1 lets a switched receptacle stand in for the lighting outlet, but only in rooms other than kitchens and bathrooms. That the exception names the kitchen at all is what tells you the kitchen is treated as a habitable room here: it needs a lighting outlet, and it cannot use the switched-receptacle substitute. A bathroom is the same. In a bedroom or living room, a wall-switched receptacle for a plug-in lamp is a compliant alternative.

The six-riser stairway rule

A stairway always needs a wall switch-controlled lighting outlet under 210.70(A)(2)(a). The riser count governs a separate question: where an interior stairway between floor levels has six risers or more, 210.70(A)(2)(c) requires a wall switch at each floor level and each landing level that includes an entryway, so no one has to climb or descend a dark flight to reach the only switch. Fewer than six risers, and a single point of control is enough. The outlet requirement does not disappear below six risers; only the each-level switching does.

Worked example: a two-story with a basement

A two-story dwelling has bedrooms, a kitchen, two bathrooms, a hallway, and a 13-riser stair to the second floor over an unfinished basement that holds the furnace and panel. Each bedroom takes a wall switch-controlled lighting outlet, and a wall-switched receptacle would satisfy it, 210.70(A)(1). The kitchen and both bathrooms take a lighting outlet with no receptacle substitute. The hallway takes one, 210.70(A)(2)(a). The 13-riser stair is six or more risers, so it takes a wall switch at each floor level and the landing, 210.70(A)(2)(c). The basement holds equipment requiring servicing, so it takes a lighting outlet at or near the furnace and panel with control at the entry, 210.70(A)(3). The exterior side of the grade-level entrances takes a wall switch-controlled lighting outlet, 210.70(A)(2)(b).

Common mistakes

  • Using a switched receptacle in a kitchen or bathroom. Exception 1 excludes both; they need an actual wall switch-controlled lighting outlet.
  • Reading a short stairway as needing no outlet. A stairway under six risers still needs a wall switch-controlled lighting outlet; only the switch-at-each-level rule is waived.
  • Assuming every attic or basement needs a light. 210.70(A)(3) applies only where the space is used for storage or contains equipment requiring servicing.
  • Skipping the light in a detached garage. A detached garage with electric power is covered by 210.70(A)(2)(a) just like an attached one.
  • Placing the storage-space light away from the equipment. 210.70(A)(3) puts the lighting outlet at or near the equipment requiring servicing, with a point of control at the usual entry.

Frequently asked questions

Does every room need a light per code?

Every habitable room and bathroom needs at least one wall switch-controlled lighting outlet under 210.70(A)(1). In a habitable room other than a kitchen or bathroom, a wall-switched receptacle may take its place.

Does a stairway need a switch at each level?

Only where the interior stairway between floor levels has six risers or more, per 210.70(A)(2)(c). Below six risers, a single wall-switch control is sufficient, and the lighting outlet itself is still required.

Does an unfinished attic need a light?

Only where it is used for storage or contains equipment requiring servicing, per 210.70(A)(3). An attic used for neither is not covered by this section.

Can I control the light with an occupancy sensor?

Yes. 210.70(A)(1) Exception 2 permits occupancy sensors that are in addition to a wall switch, or located at a customary wall switch location with a manual override that lets the sensor act as a wall switch.

Does this use the 2020 or 2023 NEC?

This tool uses the NEC 2020 text of 210.70(A). Later editions restate some of the control language; always verify against the edition your jurisdiction has adopted.

Related calculators

Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback. Going for the master license? NEC Master Electrician Exam Practice has 300 master-level questions with fully worked, table-cited answers, built on the 2023 NEC.

Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.

Already have the software and the follow-up still is not happening? That is an unfilled seat rather than a missing tool. Our own Role Build covers the seat: three duties built to run start to finish inside the tools you already pay for.

For deeper NEC training on residential lighting and dwelling wiring, Mike Holt's NEC courses are the industry standard.

Working from the printed code? NEC code books and tab sets are available from Mike Holt.