Welder Circuit Calculator
Size the supply conductor and maximum overcurrent device for a single arc welder under NEC 2020 Article 630. Enter the welder's rated primary current and duty cycle, and the tool applies the Table 630.11(A) duty-cycle multiplier, returns the smallest Table 310.16 conductor that meets it, and computes the 630.12 200 percent overcurrent ceiling.
How to use this calculator
- Pick the welder type: nonmotor-generator (transformer or inverter machines) or motor-generator.
- Enter the rated primary current and the duty cycle from the welder nameplate.
- Choose the conductor material and the termination temperature column (75 degrees C is the usual default).
- Adjust ambient temperature or conductor count if the install is not at the base Table 310.16 conditions.
- Read the required ampacity, the smallest qualifying conductor, and the maximum overcurrent device.
NEC reference
This calculator follows NEC 2020 Article 630. Section 630.11(A) and Table 630.11(A) set the supply-conductor ampacity at the rated primary current times a duty-cycle multiplier; the conductor itself comes from Table 310.16, with Table 310.15(B)(1) ambient correction and Table 310.15(C)(1) adjustment when you enter non-base conditions, and the 110.14(C) termination cap. Section 630.12(A) and (B) set the overcurrent protection at not more than 200 percent of the rated primary current and of the conductor ampacity. Article 630 is unchanged in this respect across the 2017, 2020, and 2023 editions.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
The 630.11(A) duty-cycle method
An arc welder is an intermittent load. It draws its rated primary current only while the arc is struck, and the nameplate duty cycle is the fraction of a ten-minute period the machine can run at that current without overheating. Because the conductor heats on the same intermittent schedule, NEC 630.11(A) lets it be sized to a reduced current rather than the full rated primary current: multiply the rated primary current by the Table 630.11(A) factor for the welder type and duty cycle. A welder run at a lower duty cycle draws less average heating current, so the code allows a smaller conductor.
The factors run from 1.00 at 100 percent duty down to 0.45 for a nonmotor-generator welder at 20 percent or less. Where a nameplate lists a duty cycle between the table rows, this tool rounds up to the next tabulated value, taking the larger multiplier so the conductor is never undersized.
Worked example: 50 A welder at 60 percent duty
- The nonmotor-generator welder's rated primary current is 50 A at a 60 percent duty cycle.
- The Table 630.11(A) factor for a nonmotor welder at 60 percent is 0.78.
- Required conductor ampacity is 50 x 0.78 = 39 A.
- In the 75 degrees C column of Table 310.16, 10 AWG copper is 35 A (short), and 8 AWG copper is 50 A, so the minimum conductor is 8 AWG copper.
- The overcurrent device may not exceed 200 percent of the 50 A rated primary current (100 A) or 200 percent of the 50 A conductor ampacity (100 A), so the maximum standard device is 100 A.
The two 200 percent overcurrent ceilings
NEC 630.12 caps welder overcurrent protection with two rules, both at 200 percent. Under 630.12(A) the device may not exceed 200 percent of the rated primary current; under 630.12(B) it may not exceed 200 percent of the conductor ampacity. On a single-welder branch circuit one device serves both roles, so it must satisfy both, and the smaller of the two ceilings governs. When the duty-cycle reduction lands the conductor a size or two below the welder's full rating, the conductor ceiling (630.12(B)) is usually the one that controls. Where the governing ceiling is not a standard 240.6(A) rating, 630.12 permits the next higher standard fuse or breaker.
A group of welders is sized differently
This calculator sizes the branch circuit to one welder. A feeder that supplies several welders is not the sum of their individual conductors: NEC 630.11(B) applies a diversity, taking 100 percent of the two largest welders' 630.11(A) currents, 85 percent of the third, 70 percent of the fourth, and 60 percent of the rest, on the assumption that not every machine strikes an arc at the same instant. That group feeder calculation is outside this tool's v1 scope. Resistance welders (630.31) use a separate method again, keyed on the actual and rated primary currents.
Frequently asked questions
What size wire does an arc welder need?
Multiply the rated primary current by the Table 630.11(A) duty-cycle factor, then pick the smallest Table 310.16 conductor that meets it. A 50 A nonmotor welder at 60 percent duty needs 39 A, which is 8 AWG copper at 75 degrees C.
Why can a welder conductor be smaller than the welder amps?
Because a welder is an intermittent load. It draws its rated primary current only while welding, so 630.11(A) sizes the conductor to a duty-cycle-adjusted current from Table 630.11(A) rather than the full rated current.
How is a welder overcurrent device sized?
NEC 630.12 caps it at 200 percent of the rated primary current and at 200 percent of the conductor ampacity; the smaller ceiling governs, and the next higher standard rating is permitted where that value is not standard.
What is the duty cycle multiplier for a welder?
For nonmotor-generator arc welders: 1.00 at 100 percent, 0.78 at 60 percent, 0.71 at 50 percent, 0.63 at 40 percent, 0.55 at 30 percent, and 0.45 at 20 percent or less. Motor-generator welders are slightly higher at each step.
Does the 240.4(D) small-conductor rule apply?
No. 630.12 permits welder overcurrent protection up to 200 percent of the conductor ampacity, above the 240.4(D) caps, so this tool sizes the conductor on the 630.11(A) ampacity requirement alone.
Related calculators
- Wire Ampacity Calculator: the Table 310.16 ampacity of a chosen conductor, with ambient and fill derating.
- Breaker Size Calculator: the standard 240.6(A) breaker for a general-use load with the 125 percent continuous rule.
- Motor Breaker Sizing Calculator: branch-circuit protection for a motor per NEC Article 430 and Table 430.52.
- Generator Conductor Size Calculator: generator output conductors under the NEC 445.13(A) 115 percent rule.
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
For deeper NEC training on NEC Article 630 arc welders and 630.11 conductor sizing, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.