Bonding Jumper Size Calculator
Enter the largest ungrounded supply conductor and get the minimum main bonding jumper, system bonding jumper, supply-side bonding jumper, or grounded conductor from NEC Table 250.102(C)(1), in copper or aluminum. The tool applies the Note 1 12.5% rule above 1100 kcmil copper / 1750 kcmil aluminum and handles parallel conductors by equivalent area.
How to use this calculator
- Select the largest ungrounded supply (phase) conductor and its material. This is the conductor area Table 250.102(C)(1) is indexed on, not the service rating.
- If the conductors run in parallel, enter the number of conductors per phase; the tool sums their circular-mil area before reading the table.
- Choose which conductor you are sizing (main, system, or supply-side bonding jumper, or the grounded conductor) and its material.
- Read the minimum size. The notes show the table row used, the equivalent area, and, above 1100 kcmil, the 12.5% calculation.
NEC reference
Sizing follows NEC 2020 Table 250.102(C)(1), which sets the minimum copper and aluminum grounded conductor, main bonding jumper, system bonding jumper, and supply-side bonding jumper from the size of the largest ungrounded supply conductor (or the equivalent area for parallel sets). Where the supply conductors exceed 1100 kcmil copper or 1750 kcmil aluminum, Note 1 requires the jumper to be at least 12.5 percent of the largest phase-conductor area. Table 250.102(C)(1) and its notes are unchanged across the 2017, 2020, and 2023 editions.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
NEC Table 250.102(C)(1) bonding jumper
| Largest ungrounded supply conductor (copper) | Largest ungrounded (aluminum) | Jumper copper | Jumper aluminum |
|---|---|---|---|
| 2 AWG or smaller | 1/0 AWG or smaller | 8 | 6 |
| 1 or 1/0 AWG | 2/0 or 3/0 AWG | 6 | 4 |
| 2/0 or 3/0 AWG | 4/0 AWG or 250 kcmil | 4 | 2 |
| Over 3/0 through 350 kcmil | Over 250 through 500 kcmil | 2 | 1/0 |
| Over 350 through 600 kcmil | Over 500 through 900 kcmil | 1/0 | 3/0 |
| Over 600 through 1100 kcmil | Over 900 through 1750 kcmil | 2/0 | 4/0 |
| Over 1100 kcmil | Over 1750 kcmil | 12.5% of the largest phase-conductor area (Note 1) | |
Values from NEC 2020 Table 250.102(C)(1) (identical in the 2017 and 2023 editions). Sizes are AWG unless marked kcmil. The first six rows match Table 250.66; the difference is the top row, where the bonding jumper follows the 12.5% rule instead of a fixed size.
The 12.5% rule above 1100 kcmil
Table 250.102(C)(1) stops listing discrete sizes once the ungrounded supply conductors pass 1100 kcmil copper or 1750 kcmil aluminum. Above that, Note 1 takes over: the grounded conductor or bonding jumper must have an area not less than 12.5 percent of the area of the largest set of ungrounded supply conductors. Take that area, multiply by 0.125, and round up to the next standard conductor size. A 2000 kcmil copper phase gives 0.125 x 2,000,000 = 250,000 cmil, so a 250 kcmil copper jumper. Two 600 kcmil copper conductors per phase equal 1,200,000 cmil, and 12.5 percent of that is 150,000 cmil, which rounds up to a 3/0 copper jumper.
This is exactly where Table 250.102(C)(1) parts ways with Table 250.66. The grounding electrode conductor caps at a fixed 3/0 copper (250 kcmil aluminum) no matter how large the service gets, because it feeds the earth electrode. The bonding jumper keeps scaling with the phase conductors because it has to carry fault current back to the source.
One table, four conductors
Table 250.102(C)(1) sizes four different conductors with the same numbers: the grounded (neutral) service conductor where it doubles as the fault-current path (250.24(C)), the main bonding jumper that ties the grounded conductor to the enclosure at the service (250.28), the system bonding jumper at a separately derived system (250.30(A)(1)), and the supply-side bonding jumper on the line side of the service (250.30(A)(2), 250.102(C)). Pick the one you are sizing from the dropdown; the calculator cites the governing section but the required size is identical for all four.
Parallel supply conductors
When the supply conductors are run in parallel, Table 250.102(C)(1) is read on the combined circular-mil area of the paralleled conductors in a single phase, not on one conductor. Enter the number of conductors per phase and the tool multiplies the area for you: two 250 kcmil copper conductors per phase equal 500,000 cmil, which lands in the over-350-through-600 kcmil row and calls for a 1/0 copper bonding jumper.
Bonding jumper vs. the grounding conductors
Three of Article 250's conductor tables are easy to confuse. The bonding jumper (this tool, Table 250.102(C)(1)) is sized on the supply-conductor area and bonds the fault-current path. The grounding electrode conductor (Table 250.66) is also sized on the supply-conductor area but ties the grounded service to the earth electrode, and it caps out at 3/0 copper. The equipment grounding conductor (Table 250.122) is sized on the overcurrent-device rating instead. On a 200 A service with 3/0 copper conductors, the main bonding jumper and the grounding electrode conductor are both 4 AWG copper, but the equipment grounding conductor is only 6 AWG copper. Size the other two with the Grounding Electrode Conductor Size Calculator and the Equipment Grounding Conductor Size Calculator.
Frequently asked questions
What size main bonding jumper for a 100 amp service?
A 100 A service is commonly 4 AWG copper or 2 AWG aluminum ungrounded conductors, which Table 250.102(C)(1) sizes with an 8 AWG copper (or 6 AWG aluminum) main bonding jumper. Anything 2 AWG copper or smaller lands in the same top table row.
Is the supply-side bonding jumper sized the same as the main bonding jumper?
For a wire-type jumper, yes: 250.102(C) sends both to Table 250.102(C)(1), sized on the largest ungrounded supply conductor. A supply-side bonding jumper of the busbar or raceway type is a separate construction rule, but the wire-type minimum is the same figure this calculator returns.
Can the bonding jumper be aluminum when the phase conductors are copper?
Yes. For the six tabulated rows, read the aluminum jumper column of the same row the copper conductor lands in; the table's paired columns are already ampacity-equivalent, which is what Note 2 requires. Above 1100 kcmil copper the different-material case needs the Note 2 ampacity conversion by hand, so this tool asks you to keep the jumper the same material as the supply there.
Why does the bonding jumper keep growing when the grounding electrode conductor stops at 3/0?
Because they carry current for different reasons. The bonding jumper is part of the effective ground-fault current path and must be able to carry fault current proportional to the phase conductors, so 250.102(C)(1) uses the 12.5% rule above 1100 kcmil. The grounding electrode conductor only has to reach the earth electrode, so 250.66 caps it at 3/0 copper.
Related calculators
- Grounding Electrode Conductor Size Calculator: the earth-electrode conductor from the service conductor (Table 250.66).
- Equipment Grounding Conductor Size Calculator: the equipment ground from the breaker rating (Table 250.122).
- Service Size Calculator: size the service disconnect, conductor, and grounding electrode conductor from a known load.
- Wire Size Calculator: size the ungrounded service or feeder conductors themselves.
Studying for the licensing exam? Our own NEC Code Quickstart works all twelve exam calculations start to finish, each with the code reference. Also in paperback.
Running an electrical contracting business? Jobber handles scheduling, invoicing, and job management. Start a 14-day free trial.
For deeper NEC training on grounding and bonding, Mike Holt's NEC courses are the industry standard.
Working from the printed code? NEC code books and tab sets are available from Mike Holt.
This page contains affiliate links. ElectricalToolbox may earn a commission when you sign up or buy through them, at no additional cost to you.