3-Phase Voltage Drop Calculator
Results
- Voltage drop
- —
- Percentage
- —
- Voltage at load
- —
Awaiting calculation…
Show calculation details
- Method
- —
- Resistance (R, 75°C)
- —
- Circular mils
- —
Three-phase drop uses the √3 line-to-line factor: VD = √3 × R × I × L ÷ 1000. Conductors smaller than #2 AWG use the K-factor (R = K × 1000 / circular mils, K = 12.9 copper / 21.2 aluminum). #2 AWG and larger use NEC Chapter 9 Table 9 AC resistance (PVC conduit, 75°C). Unity power factor.
Calculate line-to-line voltage drop on three-phase feeders and motor branch circuits — the long 480V runs and large 208V commercial feeders where drop actually drives conductor sizing. Results use NEC 2020 Chapter 9, Table 9 AC resistance for #2 AWG and larger, and the Table 8 K-factor for smaller conductors, at a 75°C basis and unity power factor.
How to use this calculator
- Select the line-to-line system voltage (480V, 208V, 240V, or 600V).
- Enter the load current in amps and the conductor material.
- Select the conductor size (AWG or kcmil).
- Enter the one-way distance from source to load in feet.
- Read total voltage drop, percentage, and the 3% / 5% status. If it exceeds 3%, the tool recommends the next conductor size that brings it back under 3%.
NEC reference
Three-phase voltage drop is calculated as VD = √3 × R × I × L ÷ 1000, where R is the AC resistance in ohms per 1000 ft from NEC Chapter 9, Table 9 (NEC 2020). The 3% branch-circuit and 5% combined feeder-plus-branch figures come from the informational notes to NEC 210.19 and 215.2 — they are recommendations, not requirements, unless adopted locally.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.