Wire Ampacity Calculator
Determine the allowable ampacity of a copper or aluminum conductor from NEC Table 310.16, then apply ambient temperature correction (Table 310.15(B)(1)) and adjustment for more than three current-carrying conductors (Table 310.15(C)(1)). Results include the NEC 110.14(C) termination temperature limit. NEC 2020.
Results
- Final usable ampacity
- —
- Base (Table 310.16)
- —
- After derating
- —
Awaiting calculation…
Show calculation details
- Base ampacity
- —
- Ambient correction
- —
- Conductor-count adj.
- —
- Derated ampacity
- —
- Termination limit
- —
- Governing limit
- —
- Ambient applied
- —
- Reference
- —
Final usable ampacity = min(derated, termination limit). Derating starts from the conductor's insulation column per NEC 310.15; the result is capped at the termination column per NEC 110.14(C). NEC 240.4(D) small-conductor overcurrent limits, where they apply, are shown as a note above — they are an OCPD limit, not an ampacity.
How to use this calculator
- Select conductor material, size, and insulation rating (THHN/THWN-2 is 90°C; THWN/THW is 75°C; TW is 60°C).
- Set the termination rating of the lowest-rated terminal in the circuit per NEC 110.14(C) (75°C for most modern equipment).
- Enter the ambient temperature and the number of current-carrying conductors in the raceway or cable.
- Read the final usable ampacity. The breakdown shows base ampacity, each derating factor, and which limit governs.
NEC reference
This calculator uses NEC Table 310.16 (base ampacities), NEC Table 310.15(B)(1) (ambient temperature correction), NEC Table 310.15(C)(1) (adjustment for more than three current-carrying conductors), and NEC 110.14(C) (termination temperature limitation), NEC 2020. Table 310.16 was designated Table 310.15(B)(16) in NEC 2017; ampacity values are unchanged across the 2017, 2020, and 2023 editions. NEC 240.4(D) small-conductor overcurrent limits are shown as a note where applicable.
Results are for reference only. Verify against the applicable adopted edition of the NEC and consult a licensed electrician for code compliance.
How conductor ampacity is calculated
Allowable ampacity starts as a table lookup, not a formula. NEC Table 310.16 gives the base ampacity for a conductor by material and insulation column (60/75/90°C), assuming 30°C (86°F) ambient and not more than three current-carrying conductors in the raceway. Two derating steps and one cap modify that base:
Final usable ampacity = min( base × ambient × count , termination limit )
- Ambient correction — Table 310.15(B)(1), applied when ambient differs from 30°C, read from the same insulation column.
- Conductor-count adjustment — Table 310.15(C)(1), applied when more than three current-carrying conductors share a raceway or cable.
- Termination cap — NEC 110.14(C). Derating may start from the 90°C column, but the final ampacity can\u2019t exceed the Table 310.16 value at the lowest-rated termination, typically 75°C.
The two derating factors multiply; they are not alternatives.
Worked example
6 AWG THHN copper (90°C insulation), landing on 75°C-rated terminations, in a raceway at 104°F (40°C) ambient with six current-carrying conductors:
Base (90°C col, Table 310.16) 75 A Ambient (36-40°C, ×) 0.91 Conductors 4-6 (×) 0.80 Derated 75 × 0.91 × 0.80 = 54.6 A Termination cap (75°C, 110.14(C)) 65 A Final min(54.6, 65) = 54.6 A
Derating governs here: 54.6 A is below the 65 A termination limit, so the conductor is good for 54.6 A. Drop the bundle to three conductors and the count factor disappears — the 65 A termination limit then governs instead.
Common mistakes
- Starting derating from the termination column. NEC 310.15 lets you derate from the 90°C column for a 90°C conductor; only the result is capped at the termination rating per 110.14(C). Starting from the 75°C column throws away ampacity you\u2019re entitled to.
- Forgetting 110.14(C) entirely. THHN is a 90°C conductor, but on 75°C lugs \u2014 most breakers and equipment \u2014 the usable ampacity can\u2019t exceed the 75°C column. 12 AWG copper is 30 A at 90°C, but 25 A at 75°C, and 20 A by OCPD.
- Confusing 240.4(D) with ampacity. The small-conductor rule caps overcurrent protection at 15/20/30 A for 14/12/10 AWG copper regardless of table ampacity. That\u2019s an OCPD limit, not the conductor\u2019s ampacity.
- Mis-counting current-carrying conductors. The equipment grounding conductor never counts. A neutral carrying only the unbalanced current of a multiwire circuit doesn\u2019t count; a neutral on a circuit with significant nonlinear load does (NEC 310.15(E)).
Frequently asked questions
Can I use the 90°C column for ampacity?
You can use the 90°C column as the starting point for derating, per NEC 310.15, when the conductor insulation is rated 90°C (THHN, THWN-2, XHHW-2). You generally can’t use the 90°C value as the final ampacity: NEC 110.14(C) limits the conductor to the termination temperature rating, which is 60°C or 75°C on most equipment. The 90°C column buys derating headroom, not a higher final ampacity, unless every termination in the circuit is rated 90°C — which is rare.
What’s the difference between the 60, 75, and 90°C columns?
The column is the conductor insulation’s maximum operating temperature. Higher-rated insulation carries more current in the same size because it tolerates more heat. Which column you may use is set by two things: the conductor’s own insulation rating and the termination rating per NEC 110.14(C). TW is 60°C; THW/THWN is 75°C; THHN/THWN-2 is 90°C. The 90°C column is used mainly as the derating starting point, not the final ampacity.
Does the neutral count as a current-carrying conductor?
It depends on the load. Per NEC 310.15(E), a neutral carrying only the unbalanced current from the other conductors — the typical case on a multiwire branch circuit or a balanced 3-phase wye — is not counted for conductor-count adjustment. A neutral on a 3-wire circuit from a single-phase, 3-wire system does count. A neutral carrying harmonic current from significant nonlinear loads (electronic ballasts, VFDs, switching supplies) counts. The equipment grounding conductor never counts.
How many amps can 12 AWG copper carry?
12 AWG copper is 20 A at 60°C, 25 A at 75°C, and 30 A at 90°C in NEC Table 310.16, before derating. NEC 240.4(D) separately caps overcurrent protection for 12 AWG copper at 20 A regardless of insulation, which is why 12 AWG copper is almost always on a 20 A breaker. The 30 A (90°C) figure is only a derating starting point, not a usable circuit rating.
How do I correct ampacity for high ambient temperature?
Multiply the base ampacity by the correction factor from NEC Table 310.15(B)(1) for your ambient range, read from the same insulation column you’re using as the derating start. Table 310.16 assumes 30°C (86°F); above that, factors drop below 1.0. A 90°C conductor at 40°C ambient gets ×0.91; at 50°C, ×0.82. Apply the ambient correction and the more-than-three-conductors adjustment together — they multiply — then cap at the termination rating.
What size wire do I need for a 100 A feeder?
At the 75°C termination column of NEC Table 310.16, 3 AWG copper (100 A) or 1 AWG aluminum (100 A) meets 100 A before derating. Full feeder sizing also has to account for continuous load (125% per NEC 215.3), ambient and conductor-count derating, and voltage drop over the run, so the conductor often lands larger than the bare ampacity match. Use the Wire Size Calculator to size for load, distance, and voltage drop together.
Related tools
- Voltage Drop Calculator — AC voltage drop for branch circuits and feeders.
- Wire Size Calculator — minimum conductor size for a load, from ampacity and voltage drop.
- DC Voltage Drop Calculator — voltage drop for PV, battery, and other DC circuits.